Specification Sheet

7800 SERIESS7800A2142 4Line LCD Keyboard Display Module
43 320011007
Models that do not use the Heater Function
The heater function is not available for these models that have a software revision level
starting less than 5. The heater function will not work regardless of the setting in the Heater
Mode setup. Operating Temperature from - 32 °F to 140 °F (0 °C to 60 °C).
RM7830A1003 EC7850A1122 EC7865A1005 EC7850A1007
RM7830A1029 RM7890A1064 EC7850A1148 EC7850A1015
RM7850A1001 RM7838C1020 RM7850A1035 EC7850A1031
RM7850A1019 RM7890B1055 EC7890A1037 EC7850A1049
EC7820A1026 RM7830A1011 EC7810A1001 EC7850A1056
EC7830A1033 RM7850A1027 EC7810A1019 EC7850A1106
EC7830A1058 EC7810A1027 EC7820A1000 EC7850A1114
EC7830A1066 EC7810A1035 EC7820A1018
EC7850A1072 EC7820A1034 EC7830A1009
EC7850A1080 EC7830A1041 EC7830A1017
EC7850A1098 EC7850A1064 EC7830A1025
APPENDIX B: BURNER CONTROL COMMISSIONING
The S7800 display module is required to commission the following features in 7800
SERIES burner control modules that support them:
Valve proving system
Post purge timing
Not all 7800 modules support these features. Some models may support both features
while some may only support one or the other. These safety features are configured using
a commissioning procedure that interacts with the installed burner control module. The
commissioning procedure is driven by the burner control module since it is aware of the
features it supports and is responsible for their settings. Models that support either one of
the features can be identified in the display module by one of three methods (see Fig. 64):
“SETUP NEEDED” state is displayed on the Home page
“BC Commissioning” line is present on the Home page
“BC Commissioning” line is enabled for navigation on the Display setup menu page
LINE PRESENT
FOR MODELS THAT
SUPPORT IT
INDICATES
COMMISSIONING
NEEDED
“NEXT PAGE” FOR
MODELS THAT
SUPPORT IT
Fig. 64. Commissioning applicable for burner control module
When “SETUP NEEDED” is displayed on the Home page the burner control module will not
fire until commissioning is performed. Commissioning can only be performed when the
burner control module is in this condition or when it is locked out or in a STANDBY state.
Commissioning is not allowed when the burner control module is in any other state. “BC
Commissioning” line is only present on the Home page when the burner control module
supports it and it is in one of the states listed above.
Commissioning is initiated from either the Home or Display Menu pages (see Fig. 65). The
BC commissioning setup menu displays showing the current settings of the three possible
commissionable parameters: