Specification Sheet

7800 SERIESS7800A2142 4Line LCD Keyboard Display Module
51 320011007
Message
Group
Message
Number
Text
Standard 4 Valve close
Standard 5 Burner switch
Standard 6
Operating
control
Standard 7
Auxiliary Limit
#1
Standard 8
Auxiliary Limit
#2
Standard 9
Low water cut-
off (LWCO)
Standard 10 High limit
Standard 11
Auxiliary Limit
#3
Standard 12 Oil selection
Standard 13
High oil pres-
sure
Standard 14
Low oil pres-
sure
Standard 15
High oil tem-
perature
Standard 16
Low oil tem-
perature
Standard 17 Gas selection
Standard 18
High gas
pressure
Standard 19 Gas
Low gas pres-
sure
Standard 19 Oil
Atomizing
switch
Standard 20 Airflow switch
Standard 21
Auxiliary ILK
#4
Standard 22
Auxiliary ILK
#5
Fixed 23 High water
Fixed 24 Low water
Fixed 25 High stack
Fixed 26 High blast
Fixed 27 Low pilot
Fixed 28 High pilot
Fixed 29
Combustion
damper
Fixed 30
Stack damper
PV
Fixed 31 FD fan ILK
Fixed 32
Recirculating
fan
Fixed 33 Exhaust fan
Fixed 34
Combustion
fan
Fixed 35 Oil pump
Fixed 36 Low FGR
Fixed 37
Low combus-
tion AP
Fixed 38
High tempera-
ture
Fixed 39 ControLinks
Custom 45 Default 1*
Custom 46 Default 2*
Custom 47 Default 3*
Custom 48 Default 4*
Message
Group
Message
Number
Text
Custom 49 Default 5*
Custom 50 Default 6*
Custom 51 Default 7*
Custom 52 Default 8*
Custom 53 Default 9*
Custom 54 Default 10*
Custom 55 Default 11*
Custom 56 Default 12*
Custom 57 Default 13*
Custom 58 Default 14*
Custom 59 Default 15*
Custom 60 Default 16*
Custom 61 Default 17*
Custom 62 Default 18*
Custom 63 Default 19*
Custom 64 Default 20*
* Custom message text is editable so this text can
vary.
Table 7. Annunciator Terminal Messages
Custom annunciator and Call for Service
messages can be edited using the
characters listed in the following table.
(space) A-Z a-z 0-9 . , - / : " ?
< > { } [ ] ; ““ \ | +
_ = ( ) * & ^ % $ # @
! ?
Table 8. English Character Set
When the selected language is French
or Spanish, the character set for those
languages will be shown on the display.
This table only shows the English character
set.
APPENDIX E: MODBUS
FUNCTION
See page 28 APPENDIX A: DISPLAY
SETUP for Setup.
OPERATION
The S7800 ModBusTM Data Feature
enables terminal 1, 2 to Data + and Data -.
Table 16 provides register mapping. It
identifies the mapping of the 7800 SERIES
parameters to ModBusTM registers.
Function Codes
Supported function codes of Modbus
Protocol Reference Guide (PI-MBUS-300
Rev. J) are 3, 4, 6, 16, and 17. Function
codes 3 and 4 are treated the same by the
S7800. Two registers should be read when
the data format is a U32 value (4 bytes); if
both registers are not read, then data for a
part of the value is returned. U32 values are
either in Big-endian or Little-endian format.