S9200U Installation Guide

Table Of Contents
S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
69-2075EF—05 22
Status Codes History
The S9200U1000 stores the ten (10) most recent error
codes. These codes can be recalled for viewing during
troubleshooting and cleared if necessary
Recalling the Status Code History
You may perform the following procedure multiple
times to confirm that you have viewed all the currently
stored error codes.
To recall the error code history and display it via the
red status LED, perform the following:
1. Jumper the thermostat screw-terminal R/2 to
screw-terminal D/1.
Within 0.5 seconds, the red status LED
stops normal operation and turns on solid to
indicate that the jumper is sensed.
2. Keep the thermostat screw-terminals R/2 to D/1
jumpered.
After a 5 second time-out, the red status
LED turns off, indicating that error code
recall is pending.
3. Within 10 seconds of the red status LED turning
off, remove the jumper from thermostat screw-
terminals R/2 to D/1.
This activates the error code recall.
3 + 5 Control failed Self Check, internal error, or
failed hardware (Control restarts if the error
recovers.)
This covers hardware errors like flame
sense circuit faults, pin shorts, etc.
Cycle power to appliance and run heating sequence. If this failure repeats, replace the
control.
3 + 6 Reversed Line Voltage Polarity or Poor
Earth Ground (Control restarts if the error
recovers within 5 minutes after the fault
has cleared.)
Check:
1. Line voltage input wiring. Assure line voltage hot lead is attached
to L1.
2. Ground wire from control to appliance and appliance earth ground.
3. Voltage between line volt Neutral and appliance chassis. If over 10 volts, repair the
wiring or move the furnace to another circuit with a good earth ground.
Repair: Reverse line voltage inputs if line volt hot lead is not attached to the L1 input.
Hard Lockout Codes
4 + 1 Hard Lockout - Rollout circuit open or
previously opened.
Check/Repair: Flue restrictions; heat exchanger restricted
Check burner. Check Rollout Switch including switch cables.
Reset rollout if necessary.
Do not operate until repairs are made.
Cycle power to appliance and run heating sequence.
If this failure repeats, replace the control.
4 + 2 Hard Lockout - Gas valve welded relay
detected for five times
Check/Repair: Gas valve wiring.
Cycle power to appliance and run heating sequence.
If this failure repeats, replace the control.
a
Flash Code Descriptions:
- Pulse: A 0.25 second flash followed by 3.75 seconds of off time.
- Heartbeat: Constant 0.5 second bright, 0.5 second dim cycles.
- During start-up the STATUS LED blinks fast for approximately 2 seconds. If the S9200U1000 continues
blinking fast (8 pulses/second), the control has failed and must be replaced.
- Standard LED Fault Pattern (Single X Flash): LED flashes X times at 2HZ, then off for 3 seconds.
- Advanced LED Fault Pattern (X + Y Flash): LED flashes X times at 2Hz, remains off for one second, flashes Y
times at 2Hz, remains off for three seconds, and then repeats.
Table 12. Control Status Codes (Red LED). (Continued)
Flash
Code
a
Red LED Status Code and Error
Description Check / Repair
Table 13. E-COM Status Codes (Green LED).
Flash Code Green LED Status Code and Description
a
a
This LED is active even if a conventional thermostat is controlling the appliance.
Check / Repair
Rapid
Flashing
Bus Activity - Message being transmitted Not Applicable (normal operation)
Single Blink Bus Activity - Received message acknowledgment Not Applicable (normal operation)
Off No Bus Activity Check/Repair: Disconnect the S9200U1000 from the external bus wiring,
cycle power and check the bus activity. If there is activity, repair external
bus wiring/devices before reconnecting the S9200U1000.
If there is still no activity, replace the control.