S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
23 69-2075EF—05
IMPORTANT
If the R/2 to D/1 terminal jumper is not
removed within the 10 seconds, the history is
erased.
4. Each saved error code blinks once on the red
status LED, starting with the most recently
stored error code.
NOTE: If there are no error codes to display, the red
status LED immediately returns to normal
operation.
5. After last error code displays, the red status LED
returns to normal operation.
Clearing the Status Code History
This procedure erases the entire history of fault (error)
codes.
IMPORTANT
Once this procedure is performed, it cannot be
undone.
To clear the current error code history, perform the
following:
1. Jumper the thermostat screw-terminal R/2 to
terminal D/1.
Within 0.5 seconds the red status LED stops
normal operation and turns on solid to
indicate that the jumper is sensed.
2. Keep the thermostat screw-terminal R/2 to D/1
jumpered.
After a 5 second time-out, the red status
LED turns off.
After a 10 second time-out, the red status
LED turns on solid to indicate that the error
history is being cleared.
3. When the error history is cleared, the red status
LED returns to normal operation.
4. Remove the thermostat screw-terminal R/2 to
terminal D/1 jumper.
EnviraCOM
Communication
EnviraCOM™ communication is a standard feature on
the S9200U1000. EnviraCOM™ can be used to control
system operation by way of an EnviraCOM™ enabled
thermostat and perform advanced diagnostics when
connected to EnviraCOM™ enabled diagnostic tools
such as the web based EnviraLNK® remote
diagnostics application, the OnWatch QuickLook™ 72
and the W8735D Telephone Access Module (TAM). In
addition to alarms, key information such as state and
flame current can be sent over the EnviraCOM™ bus.
See Table 14.
.
Table 14. S9200U1000 EnviraCOM™ Alarms.
Alarm Description
Alarm
Number Comment
This device has no alarms 0 Not Applicable
Pressure switch failed to close in the ignition sequence 1 Display/Diagnostics
Pressure switch failed to open in the ignition sequence 3 Display/Diagnostics
Flame current caution level while running 4 Display/Diagnostics
Soft lockout due to flame current 5 Display/Diagnostics
The maximum number of flame loss incidents has been exceeded 22 Display/Diagnostics
Limit switch open 26 Display/Diagnostics
Flame detected out of sequence 34 Display/Diagnostics
Soft Lockout due to recycle; last recycle was from pressure switch open 85 Display/Diagnostics
Soft Lockout due to recycle; last recycle was from limit switch open 86 Display/Diagnostics
The pressure switch opened in run or trial for more than the allowable time 98 Display/Diagnostics
Gas valve failed to energize 17 Display/Diagnostics/EnviraLNK®/TAM
Electronics down 18 Display/Diagnostics/EnviraLNK®/TAM
Reversed line polarity 33 Display/Diagnostics/EnviraLNK®/TAM
A manual reset is required due to Rollout Limit 87 Display/Diagnostics/EnviraLNK®/TAM
Earth ground problem 88 Display/Diagnostics/EnviraLNK®/TAM
A bad fuse has been detected (NOTE: This alarm is stored in the Status Code History) 92 Display/Diagnostics/EnviraLNK®/TAM
The gas valve relay was sensed as closed when it should be open 100 Display/Diagnostics/EnviraLNK®/TAM
A manual reset is required due to gas valve welded condition being detected more times
than allowed maximum
124 Display/Diagnostics/EnviraLNK®/TAM
Low voltage is detected on 24 Vac input 125 Display/Diagnostics/EnviraLNK®/TAM