S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
Home and Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
® U.S. Registered Trademark
© 2018 Honeywell International Inc.
69-2075EF—05 M.S. Rev. 08-18
Printed in United States
Test Mode
The S9200U1000 is equipped with a Test Mode
feature which allows the control to test and verify
several critical parameters. During Test Mode, the
S9200U1000 alters the selected Safety Timings as
described in Table 15.
Test Mode can be accessed several ways:
— Thermostat inputs:
• Apply a Y + G request within 3 seconds after
power-up for 2 seconds.
• Next, remove the Y + G request and apply W
request within 10 seconds.
— EnviraCOM™ command
— The G signal enables the circulator in Test
Mode. If a G request is present, the circulator
is controlled as required by the heating or
cooling sequence. If the G request is removed,
the circulator turns off during the heating or
cooling sequence. If there is no other thermo-
stat request present, a G request causes the
circulator to be energized. The circulator ener-
gizes during a heating cycle if the limit switch
opens, regardless of the G signal.
If there is a failure during Test Mode:
• An error code flashes indicating the failure.
See Table 12 on page 21.
• An EnviraCOM™ alarm is active and sent on
the bus. See Table 14 on page 23.
Test Mode is exited after any of the following
conditions:
— Three minutes of operation
— Receipt of an EnviraCOM™ command instruct-
ing the S9200U1000 to exit Test Mode
—The cycling of power
QuickLook™ 72 is a trademark of OnWatch Electronics Inc.
EnviraCom™ is a trademark of Honeywell.
EnviraLNK® is a registered trademark of Honeywell.
Table 15. Test Mode Parameters.
Test Mode Parameter Modified Timing
Pre-Purge 5 seconds
HSI Warm-up 17 seconds
Ignition Activation 3 seconds
Flame Recognition 1 second
Trial for Ignition 4 seconds
Heat Fan ON Delay 15 seconds
Heat Fan OFF Delay 0 seconds
Post-Purge 5 seconds
Cool Fan ON Delay 2 seconds
Cool Fan OFF Delay 0 seconds