user manual

ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
198
11.3 Clearing the “#” Symbol From SFC Display, Continued
Procedure, continued
Table 60 Clearing the # Symbol from the SFC Display, continued
If Message is. . . Then, Possible Cause is. . . And, Suggested Corrective
Action is. . .
#T 011P3
OAD.OM. E
ST ATUS
RVBL
OR
#T 011P3
AULROET Y
ST ATUS
DEFMB T
Pressure input is two times
greater than URL of transmitter.
Check range and, if required,
replace transmitter with one that
has a wider range.
Meter body may have been
damaged. Check the transmitter
for accuracy and linearity
Replace meter body and
recalibrate, if needed.
#
T 0 1 1 P 3
C O M A O E
S T A T U S
T D P N C P M
No temperature compensation
data exists for D/A converter.
Effect will be minor degradation of
ambient temperature influence
specifications. Replace electronics
module
#T 011P3
TEMOEV
ST ATUS
OSRSR PEN
Meter body temperature is too
high. Accuracy and life span may
decrease if it remains high.
Take steps to insulate meter body
from temperature source.
#T 011P3
ON
ST ATUS
NUWKN
Selection is unknown Be sure SFC software is latest
version. Press SHIFT and 3 to view
SFC software version.