Operation
Activation of a compatible smoke detector or any normally-open
fire alarm initiating device activates audible and visual signaling
devices, illuminates an indicating LED, sounds the piezo
sounder at the FACP, activates the FACP alarm relay and oper-
ates an optional module used to notify a remote station or initi-
ate an auxiliary control function.
Specifications
AC POWER — TB3
SFP-2404: 120 VAC, 50/60 Hz, 2.3 A.
SFP-2404E: 240 VAC, 50 Hz, 1.15 A.
Wire Size: Minimum 14 AWG (2.0 mm²) with 600 V insulation.
BATTERY (SEALED LEAD-ACID ONLY) — J8
Maximum charging circuit: normal flat charge 27.6 VCD @
0.8 A.
Maximum battery charger capacity: 18.0 AH battery (two
7.0 AH batteries can be housed in the FACP cabinet. Larger
batteries require a separate battery box such as the Notifier
BB-17).
INITIATING DEVICE CIRCUITS — TB3
Alarm zones 1 - 4.
Power-limited circuitry.
Operation: all zones Style B (Class B).
Normal operating voltage: nominal 20 VDC.
Alarm current: 15 mA minimum.
Short-circuit current: 40 mA maximum.
Maximum loop resistance: 100 ohms.
End-of-line resistor: 4.7K ohm, ½ watt (P/N 71252).
Standby current: 4 mA.
Compatible devices: refer to the
Notifier Device Compatibility
Document
PN 15378 for a complete list of compatible
devices.
NOTIFICATION APPLIANCE CIRCUITS — TB2
•Two NACs.
Power-limited circuitry.
Normal operating voltage: nominal 24 VDC.
Maximum signalling current: 2.5 A total with standard trans-
former 5.0 A total (2.5 A maximum per NAC) with optional
transformer.
End-of-line resistor: 4.7K ohm, ½ watt (P/N 71252).
Compatible devices: refer to the
Notifier Device Compatibility
Document PN 15378 for a complete list of compatible
devices.
FORM-C RELAYS
Trouble Relay TB5 (fail-safe).
Alarm Relay TB6.
Supervisory relay TB7.
Relay contact ratings: 2.0 A @ 30 VDC (resistive).
AUXILIARY OUTPUT: RESETTABLE POWER — TB1
Operating voltage: nominal 24 VDC.
Maximum available current: 500 mA — appropriate for pow-
ering four-wire smoke detectors (see notes).
Power-limited circuitry.
Notes: 1) Refer to the Notifier Device Compatibility Document
for a complete list of compatible devices.
2) Total current for nonresettable power, resettable power and
two NACs must not exceed 6.0 A for the SFP-2404 (required
optional second transformer).
CABINET DIMENSIONS
Door: 15.342” (38.97 cm) high x 14.667” (37.28 cm) wide x
0.375” (0.95 cm) deep.
Backbox: 15.0” (38.10 cm) high x 14.5” (36.83 cm) wide x 3.0”
(7.62 cm) deep.
BACKBOX MOUNTING
The cabinet can be surface mounted. The door is removable
during installation by opening and lifting it off the hinges. The
cabinet mounts using two key slots at the top of the backbox and
two additional 0.25” diameter holes at the bottom.
Listings and Approvals
UL Listed: S635
MEA: 297-01-E Vol. II
CSFM: 7165-0028:220
Ordering Information
SFP-2404: Four-zone conventional FACP; 120 VAC, 50/60 Hz,
2.3 A.
SFP-2404E: Same as above, but 240 VAC, 50 Hz, 1.15 A opera-
tion.
CAC-4: Class A converter module. Used to convert Style B
(Class B) IDC to Style D (Class A) and Style Y (Class B) NAC to
Style Z (Class A). The module connects to J1 on the SFP-2404
circuit board.
4XTM: Transmitter module.
4XLM: LED interface module.
4XZM: Zone relay module, 4 form C relay.
BB-17: Battery box, required to house two batteries greater
than 7 AH to a maximum of 18 AH.
411/411UD: Three-input (channels) model 411, and four-input
model 411UD, dual-line Digital Alarm Communicator/Transmit-
ters (DACTs). Can be used as slave communicators with the-
FACP.
TR-1-B: Optional trim ring for semi-flush mounting.
A 2-zone version of this panel is also available. See DN-6876.