General Specifications
Sensitivity
Adjustable between 60 ft., 45 ft., 30 ft, and 15 ft. to a 1 sq. ft. gasoline fire
Response Time 2-5 seconds to 1 sq. ft. of gasoline fire at 60 ft.
Field-of-View 120 degrees cone of vision (60 degrees from on axis).
Spectral Sensitivity Ultraviolet: 185 to 260 nanometers
Wide Band Infrared: 0.7 to 3.5 micrometers (SS4-A and SS4-AS only)
Visible: 400 to 700 nanometers (SS4-A and SS4-AS only)
Input Power 24 VDC nominal (20.5 to 34 VDC)
Power Consumption 68 mA normal operation (relay version)
75 mA alarm condition (relay version)
95 mA alarm condition (analog version)
Output Relays Fire Alarm Relay: NO & NC contacts
Latching/Non-Latching, switch selectable
Fire Verify Relay: NO & NC contacts
Adjustable time from 0 to 30 seconds
Fault Relay NO & NC contacts
Relay contact ratings: 0.5A at 120 VAC, 1.0A at 24VDC
Fault relay is energized during normal operation
All other relays are de-energized
Operating Temperature -40 to 185°F (-40 to 85°C)
Humidity Range 5 to 98% RH, non-condensing
Weight 4 pounds - Aluminum
7.5 pounds - Stainless Steel
Housing Copper-free aluminum (less than 0.4%) powder coated NEMA4 (IP66), tamper
resistant with integral dual ¾” NPT conduit openings or optional M25.
Stainless steel housing available
Electrical Classification Explosion-proof
Class I, Div. 1 & 2, Groups B, C and D
Class II, Div. 1 & 2, Groups E, F and G
Class III
Vibration Meets or exceeds MIL Spec 810 C Method 514.2, Curve AW
Mounting Swivel bracket assembly
Warranty Two years from factory shipping date
Maximum Sensitivity
Field of View, Horizontal and Vertical
Sensitivity to 1 sq. ft. Gasoline Pan Fire
Maximum Sensitivity
Field of View, Horizontal and Vertical
Sensitivity to 1 sq. ft. Gasoline Pan Fire
Distence
General Dimensions
Side and Back Views
(All Dimensions in Inches)
60Ft 40Ft 30Ft 15Ft
15°
30°
45°
60°
120 度
4.29
1.71
4.35
2.35 2.00
1.06
”NPT
3
4
6.16
5.50
4.89
4.75
Ф4.89
FSC
firealarmresources.com