Specifications

SmartValve® System Controls
70-6910 127
Home
Controls Indoor Air Quality
Residential
Combustion Controls Hydronic Controls
Water
Controls Building Automation
Commercial
Components Pneumatic Controls
Industrial Combustion
Controls
SV9641 SmartValve® System
The TRADELINE® SV9641 SmartValve System Controls combine
gas flow control and electronic intermittent pilot sequencing
functions into a single unit. The Q3450 or Q3480 Pilot hardware
supplies the low voltage igniter, flame sensor and pilot burner.
These ignition system controls provide all gas ignition safety
functions by controlling gas flow, ignition source, and a 120 Vac or
240 Vac combustion air blower. The controls also monitor the
appliance airflow proving switch and limit string to assure proper
appliance operation, and provide prepurge, postpurge, and timed
trial for pilot ignition with 100 percent shutoff and continuous retry.
A diagnostic LED indicates system status.
These controls communicate directly with an electronic fan timer
(ST9160 Electronic Fan Timer for single stage applications; ST9162
Electronic Fan Timer for two-stage applications) in typical forced
warm air furnace applications.
They also interface with the 208907 Terminal Board, providing
compatibility with power stealing thermostats. Or, they directly
interface with the appropriate power supplies and a system
thermostat for additional appliance applications.
When controlled directly by a thermostat, these controls do not
provide a postpurge function, because power to the control is
removed when the thermostat call for heat ends.
The SV9641 Systems are suitable for a wide range of fan-assisted
combustion gas-fired appliances including furnaces, rooftop
furnaces, boilers, unit heaters, infrared heaters, water heaters and
commercial cooking appliances.
Dimensions, Approximate: 3.2 in. wide x 4.9 in. high x 4.1 in. long
(81 mm wide x 124 mm high x 104 mm long)
Body Pattern: Straight-through
Maximum Capacity at 1 in. P.D. 300 ft
3
/hr (8.5 m
3
/hr)
Maximum Capacity: 415 ft
3
/hr (11.8 m
3
/hr)
Minimum Capacity: 30 ft
3
/hr (0.8 m
3
/hr)
Pilot Gas Outlet: Yes
Electrical Ratings: 24 Vac
Frequency: 60 Hz, 50 Hz
Control Voltage (Thermostat or other call for heat): 24 Vac
Flame Failure Response Time (sec): 1.6 sec @ 3 µA
Flame Sense: Two Rod
Ignition Sequence: Intermittent Pilot
Ignition Source: Pilot
Ignition System Type: Intermittent Hot Surface Pilot Ignition
Ignition Trial Time: 90 sec
Ignition Trials To Lockout: continuous retry
Pressure Ratings: 1/2 psi (3.5 kPa)
Pressure Tapping: 1/8 in. - NPT
Ambient Temperature Range: -40 F to +175 F (-40 C to +79 C)
Mounting: 0 to 90 degrees in any direction from the upright position of
the gas control knob, including vertically.
Product Number
Type of
Gas
Opening
Characteristics
(standard, step)
Inlet/Outlet
Size (in.)
Pressure Regulator
Setting
PrePurge PostPurge Includes(psi) (kPa)
SV9641M4510 Natural Standard Opening 3/4 in. NPT x
3/4 in. NPT.
0.87 kPa 3.5 in. wc 15 seconds 30 seconds Two 3/4 in. x 1/2 in. reducer
bushings and an LP conversion kit.
* TRADELINE models • SUPER TRADELINE models