Specifications

Thermostatic Radiator Valves and Actuators
268 customer.honeywell.com 70-6910
Typical Installations
Capacity: Standard
Materials (Body): Nickel Plated Bronze
Differential Pressure Rating:
With T100 or T200: 15 psi (103 kPa)
With MV100: 36 psi (248 kPa)
For low noise: 3 psi (20 kPa)
Pressure Ratings (Hot Water): 150 psi maximum
(1034 kPa maximum)
Pressure Ratings (Steam): 15 psi maximum (103 kPa)
Temperature Rating: 248 F Maximum (120 C Maximum)
Cartridge Change Tool: Yes - Use VA8200A001
M4640
M4638
M3190
M4632
Product Number Application Body Pattern
Pipe Size Outlet
Connection
Type
Capacity
Used With(inch) DN (Cv) (Btu/hr-steam)
V200LDSL15 For baseboards and other
installations with copper
tubing.
Straight 1/2 in. DN15 Sweat both
ends, no union
2.5 Cv 59,100 Btu/hr T100
V200LDSL20 Straight 3/4 in. DN20 Sweat both
ends, no union
2.7 Cv 63,800 Btu/hr T100
V2040ASL15 Replaces most manual
valves with minimum piping
changes.
Horizontal Angle 1/2 in. DN15 Threaded 2.5 Cv 59,100 Btu/hr T100A, M and V controls
to conform to horizontal
mounting requirements
V2040ASL20 Horizontal Angle 3/4 in. DN20 Threaded 2.7 Cv 63,800 Btu/hr T100A, M and V controls
to conform to horizontal
mounting requirements
V2040ASL25 Horizontal Angle 1 in. DN25 Threaded 2.7 Cv 70,500 Btu/hr T100A, M and V controls
to conform to horizontal
mounting requirements
V2040DSL15 Especially suited for base
boards and straight runs
where manual valves were
not originally installed.
Straight 1/2 in. DN15 Threaded 2.5 Cv 59,100 Btu/hr
V2040DSL20 Straight 3/4 in. DN20 Threaded 2.7 Cv 63,800 Btu/hr
V2040DSL25 Straight 1 in. DN25 Threaded 2.7 Cv 70,500 Btu/hr
V2040ESL15 Use where installation
space is limited
Angle 1/2 in. DN15 Threaded 2.5 Cv 59,100 Btu/hr T100B; T100C; T100F
V2040ESL20 Angle 3/4 in. DN20 Threaded 2.7 Cv 63,800 Btu/hr T100B; T100C; T100F
V2040ESL25 Angle 1 in. DN25 Threaded 2.7 Cv 70,500 Btu/hr T100B; T100C; T100F
V2043ASL15 Replaces most manual
valves with minimum piping
changes.
Horizontal Angle 1/2 in. DN15 Sweat 2.5 Cv 59,100 Btu/hr T100A, M and V controls
to conform to horizontal
mounting requirements
V2043ASL20 Horizontal Angle 3/4 in. DN20 Sweat 2.7 Cv 63,800 Btu/hr T100A, M and V controls
to conform to horizontal
mounting requirements
V2043DSL15 For baseboards and other
installations with copper
tubing.
Straight 1/2 in. DN15 Sweat both
ends, no union
2.5 Cv 59,100 Btu/hr T100
V2043DSL20 Especially suited for base
boards and straight runs
where manual valves were
not originally installed.
Straight 3/4 in. DN20 Sweat 2.7 Cv 63,800 Btu/hr
V2043ESL15 Use where installation
space is limited
Angle 1/2 in. DN15 Sweat 2.5 Cv 59,100 Btu/hr T100B; T100C; T100F