With a disconnected or failed
T7770, or a T7350 set for local
temperature sensing, offset is zero.
Using Temporary Occupied Override
The Temporary Occupied Override can be used
when the T7350 is in Not Occupied or Standby
mode. It switches to the Occupied mode for a
fixed number of hours.
1. To use the default occupied override,
press Temporary Occupied.
NOTE: The default temperature setting
is the Occupied setpoint.
2. To select a temperature setting other than
the default, press upor down
until desired temperature offset displays
(range is 0°F to 3°F).
Using Temporary Not Occupied
Override
The Temporary Not Occupied Override fixes the
device to operate in Not Occupied mode for a
number of days (between 1 and 99) without
changing the programming saved in memory.
NOTES:
If the number of days is set to zero,
no temporary change takes effect.
If the number of days is set just
below zero, the display for days is
“---” (an indefinite override).
To turn off this override, you must
press Run Schedule.
1. Press Temporary Not Occupied.
2. Press upor down to change the
duration of the Not Occupied period (in
days).