Install Instructions

T775P SERIES 2000 CONTROLLER 1. SETUP
62-0256–03 18
Fig. 36. Setup - Outputs - Options - Off Delay.
1.3.3.5. OFF DELAY
This is the minimum time delay between consecutive OFF
stages.
1. From the Options menu, use the Sand T buttons
to highlight OFF DELAY, then press the X button to
display the interstage off delay.
2. Use the S and T buttons to increase/decrease the
off delay time from 0 to 990 seconds in increments
of 10 seconds.
Default: 0 (zero) seconds
Range: 0 to 3,600 seconds in 10 second
increments
There is a built-in minimum delay of 1 second
between stages upon energizing.
3. Press the X button to accept the value and display
the Options menu.
Fig. 37. Setup - Outputs - Options - WWSD.
1.3.3.6. WWSD
This option selects the warm weather shutdown for
stages.
1. From the Options menu, use the Sand T buttons
to highlight WWSD, then press the X button to
display the value.
2. Use the S and T buttons to select the value.
Default: NO
3. Press the X button to accept the value and display
the Options menu.
If YES is selected, the WWSD TEMP item appears in the
Options menu.
Fig. 38. Setup - Outputs - Options - WWSD.
1.3.3.7. WWSD TEMP
The option for the warm weather shutdown temperature
for stages displays when the WWSD option is selected as
YES.
1. From the Options menu, use the Sand T buttons
to highlight WWSD TEMP, then press the X button
to display the warm weather shutdown temperature.
2. Use the S and T buttons to increase/decrease the
temperature.
Default: 65°F (18°C)
Range: 30 to 100°F (-1 to 38°C)
3. Press the X button to accept the value and display
the Options menu.
SETUP
OUTPUTS
OPTIONS
OFF DELAY
SETUP
OUTPUTS
OPTIONS
OFF DELAY
0
SEC
ENTER
TIME FOR
INTER-
STAGE
OFF DELAY
M24663
USE WARM
WTHR SHTDN
FOR
STAGES
SETUP
OUTPUTS
OPTIONS
WWSD
M24664
YES
NO
SETUP
OUTPUTS
OPTIONS
WWSD
ENTER WARM
WTHR SHTDN
TEMP FOR
STAGES
SETUP
OUTPUTS
OPTIONS
WWSD TEMP
M24665
65
F
o
SETUP
OUTPUTS
OPTIONS
WWSD TEMP