Install Instructions

1. SETUP T775P SERIES 2000 CONTROLLER
23 62-0256–03
Fig. 53. Setup Pump Exit.
1.3.7.4. Pump Exit
Press the W button (or highlight EXIT and press the X
button) to exit the current Stage/Pump menu and return to
the Outputs menu.
This completes the pump setup. Continue with “1.4. Setup
Alarms”.
Fig. 54. Setup Alarms.
1.4. Setup Alarms
1. From the Setup menu, use the S and T buttons to
highlight the Alarms.
2. Press the X button to display the Alarms menu.
There are three alarms available, High, Low, and
Differential. When an alarm is selected, its alarm limit
selection displays on the Alarms menu.
When an alarm is active, the Digital Output (D.O.) closes
and “ALARM” displays on the home screen.
Fig. 55. Setup High Alarm.
1.4.1. HIGH ALARM
Only Sensor A can be used to sense the high alarm
temperature. Sensor C cannot be used.
1. From the Alarms menu, use the S and T buttons
to select HI ALARM.
2. Press the X button to display the alarm options.
3. Use the S and T buttons to select YES or NO.
Default: NO
4. Press the X button to accept the value and display
the Alarms menu.
Selecting YES displays the HI LIMIT option on the Alarms
menu once you exit this screen. Continue with “1.4.1.1.
HIGH LIMIT” on page 23.
For systems with no high limit alarm, select NO, press
the X button, and continue with “1.4.2. LOW ALARM” on
page 24.
Fig. 56. Setup High Alarm Limit.
1.4.1.1. HIGH LIMIT
1. From the Alarms menu, use the Sand T buttons to
highlight HI LIMIT.
2. Press the X button to display the high alarm limit
temperature.
3. Use the S and T buttons to increase/decrease the
temperature.
Default: 220°F (104°C)
Range: -10 to 248°F (-23 to 120°C)
4. Press the X button to accept the value and display
the Alarms menu.
SETUP
OUTPUTS
STG4/PUMP
RESET RT
PUMP OUT
EXERCISE
PREPURGE
POSTPURGE
EXIT
M24680
SETUP
ALARMS
M24681
HI ALARM
LO ALARM
DIF ALARM
EXIT
SETUP
ALARMS
SETUP
ALARMS
HI ALARM
M24682
YES
NO
ENABLE
HIGH
LIMIT
ALARM
SETUP
ALARMS
HI ALARM
ENABLE
ALARM
HIGH
LIMIT
SETUP
ALARMS
HI LIMIT
M24683
220
F
o
SETUP
ALARMS
HI LIMIT