Install Instructions

T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—05 14
Fig. 28. Program - Sensor A Max. Setpoint.
1.2.2. SP MAX A1 or BOILER MAX
Setpoint maximum for Sensor A.
1. From the menu, use the S and T buttons to
highlight BOILER MAX or SP MAX A1.
2. Press the X button to display the maximum setpoint
value.
3. Use the S and T buttons to increase/decrease the
desired maximum setpoint temperature.
Default: 180° F (82° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the setpoint
temperature and display the next option.
Fig. 29. Program -Sensor B Max. Setpoint.
1.2.3. RESET B1 or OUTSD MIN
Sensor B value when at SP MAX A1 Setpoint.
1. From the menu, use the S and T buttons to
highlight RESET B1 or OUTSD MIN.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 10° F (-12° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the value and display
the next option.
Fig. 30. Program - Sensor A Min. Setpoint.
1.2.4. SP MIN A2 or BOILER MIN
Setpoint minimum for Sensor A B value when at SP MAX
A1 Setpoint.
1. From the menu, use the S and T buttons to
highlight BOILER MIN or SP MIN A2.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired minimum setpoint temperature.
Default: 140° F (60° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the setpoint
temperature and display the next option.
Fig. 31. Program - Sensor B Min. Setpoint.
1.2.5. RESET B2 or OUTSD MAX
Sensor B value when at MIN A2 Setpoint.
1. From the menu, use the S and T buttons to
highlight RESET B2.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 60° F (16° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the value and display
the next option.
ENTER
MAXIMUM
SETPOINT FOR
SENSOR A
PROGRAM
RELAY 1
SP MAX A1
MENU
PROGRAM
RELAY 1
SP MAX A1
210
F
o
M24307
ENTER
SENSOR B VALUE
FOR MAXIMUM
SETPOINT
PROGRAM
RELAY 1
RESET B1
MENU
PROGRAM
RELAY 1
RESET B1
20
F
o
M24308
PROGRAM
RELAY 1
SP MIN A2
MENU
PROGRAM
RELAY 1
SP MIN A2
ENTER
MINIMUM
SETPOINT FOR
SENSOR A
160
F
o
M24309
ENTER
SENSOR B VALUE
FOR MINIMUM
SETPOINT
PROGRAM
RELAY 1
RESET B2
MENU
PROGRAM
RELAY 1
RESET B2
70
F
o
M24310