Install Instructions

T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—05 30
Fig. 75. Setup - Outputs - Relay - Reset.
3.3.6.3. RESET
The Reset menu displayed (Fig. 75) depends on whether
the controller has modulating outputs:
For controllers with modulating outputs, the first output
(MOD 1) is settable for Reset, which then enables
Reset to be set for the Relay outputs. Refer to
“3.3.3.1.6. RESET” on page 25.
For controllers with no modulating outputs, this
selection enables the controller’s Reset function, and
allows each relay output to be individually programmed
for Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first output (MOD 1 or Relay 1 depending on the
model) must be set for Reset.
1. Press the X button to display the Reset values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
If you select YES, then all other outputs display this
Setup option and will use the reset curve programmed
for the first output.
If you select NO, then No Reset is configured for that
output and all other subsequent outputs.
Fig. 76. Setup - Outputs - Relay - Reset Runtime.
3.3.6.4. RESET RT (run time)
This selection displays only if “Show RT = YES” is
selected during Output Options setup (Refer to page 27).
1. Press the X button to display the Reset RT values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each
individual relay. You must do this for each relay
that you want to reset to zero.
3.3.7. Setup the Next Relay
To setup the next relay output go to “3.3.6. Setting up the
Relays” on page 27.
3.4. Exiting Setup
Press the W button to exit the selected relay set up and
return to the Outputs menu.
If you are finished setting up the relay outputs, press the
HOME button to exit Setup mode and return to the home
screen display.
This completes the Setup procedure.
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES-BOILER
YES-OTHER
NO
CONTROLLERS WITH MODULATING OUTPUTS
CONTROLLERS WITH NO MODULATING OUTPUTS
SETUP
OUTPUTS
RELAY 1
RESET
SETUP
OUTPUTS
RELAY 1
RESET
M24356
SETUP
OUTPUTS
RELAY 1
RESET RT
SETUP
OUTPUTS
RELAY 1
RESET RT
RESET
RUN TIME
FOR
RELAY 1
YES
NO
M24357