Install Instructions

T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
17 62-0249—05
Fig. 38. Program Menu - No Reset.
2.1.1. Program Menu for Outputs with No Reset
Press the MENU button, select PROGRAM, then highlight
the MOD or Relay desired and press the X button to view
the parameters. Fig. 38 shows RELAY 1.
NOTE: For MOD 1 and 2, THROT RNG replaces
DIFFRNTL.
NOTE: The Setback parameter displays only if
scheduling is enabled (Refer to Fig. 64 on page
26) or the DI Option is set to Setback. (Refer to
Fig. 66 on page 27).
Continue with “2.1.2. SETPOINT”.
Fig. 39. Program - Setpoint.
2.1.2. SETPOINT
1. From the menu, use the S and T buttons to
highlight SETPOINT.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 70° F (21° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the setpoint
temperature and display the next option.
Fig. 40. Program - Differential or Throttling Range.
2.1.3. DIFFERENTIAL or THROTTLING RANGE
Differential displays for the Relay outputs and Throttling
Range is used for Modulating outputs.
1. From the menu, use the S and T buttons to
highlight DIFFRNTL or THROT RNG.
2. Press the X button to display the throttling range
value.
3. Use the S and T buttons to increase/decrease the
desired value.
Default: 20° F (-6.6° C)
Range: 1° to 150° F (1° to 66° C)
4. Press the X button to accept the value and display
the next option.
NOTES:
a. In heating mode, the Differential is below the
setpoint. The relay de-energizes when the
temperature rises to the setpoint. As the temperature
drops to the setpoint minus the Differential, the relay
energizes.
b. In cooling mode, the Differential is above the
setpoint. The relay de-energizes when the
temperature falls to the setpoint. As the temperature
rises to the setpoint plus the Differential, the relay
energizes.
c. The Throttling Range brackets the setpoint
setting, e.g., if the setpoint is 72°F (22° C) and the
throttling range is 10° F (-12° C), then the effective
throttling temperature range is 67° to 77° F (19° to
25° C). This applies to both modulating outputs
and floating outputs.
PROGRAM
RELAY 1
MENU
PROGRAM
RELAY 1
SETPOINT
DIFFRNTL
SENSOR
HEAT/COOL
SETBACK
EXIT
M24315
ENTER
SETPOINT
FOR
RELAY 1
PROGRAM
RELAY 1
SETPOINT
MENU
PROGRAM
RELAY 1
SETPOINT
70
F
o
M24316
ENTER
DIFFERENTIAL
FOR
RELAY 1
PROGRAM
RELAY 1
DIFFRNTL
MENU
PROGRAM
RELAY 1
DIFFRNTL
20
F
o
M24317