Install Instructions

T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
29 62-0249—05
Fig. 72. Setup - Outputs - Floating Relay - Integral.
3.3.6.1.1.2. INTEGRAL (modulating/floating relay only)
The Integral option displays only on the T775R2001 and
the T775R2035 models when the Type option = Floating.
1. From the menu, use the S and T buttons to
highlight INTEGRAL.
2. Press the X button to display the actuator value.
3. Use the S and T buttons to increase/decrease the
desired number of seconds.
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the X button to accept the value and display
the DERIVATIV option.
Refer to Integral NOTES on page 24 for additional
information about setting the Integral time.
Fig. 73. Setup - Outputs - Floating Relay - Derivative.
3.3.6.1.1.3. DERIVATIV (modulating/floating relay only)
The Derivative option displays only on the T775R2001
and the T775R2035 models when the Type option =
Floating.
1. From the menu, use the S and T buttons to
highlight DERIVATIV.
2. Press the X button to display the actuator value.
3. Use the S and T buttons to increase/decrease the
desired number of seconds.
Default: 0 seconds
Range: 0 to 3,600 seconds)
4. Press the X button to accept the value and display
the SCHEDULE option.
Continue with “3.3.6.2. SCHEDULE” for the remaining
relay selections.
Fig. 74. Setup - Outputs - Relay - Schedule.
3.3.6.2. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (Refer to
page 26). When selected, individual outputs default to
follow the schedule.
1. Press the X button to display the Schedule values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Relay menu.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
SETUP
OUTPUTS
FLOAT 1
INTEGRAL
ENTER
INTEGRAL
TIME FOR
FLOAT 1
SETUP
OUTPUTS
FLOAT 1
INTEGRAL
400
SEC
M24353
SETUP
OUTPUTS
FLOAT 1
DERIVATIV
ENTER
DERIVATIVE
TIME FOR
FLOAT 1
SETUP
OUTPUTS
FLOAT 1
DERIVATIV
0
SEC
M24354
SETUP
OUTPUTS
RELAY 1
SCHEDULE
SETUP
OUTPUTS
RELAY 1
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24355