Fig. 54. Setup - Outputs - Relay - Reset.
1.3.4.2. RESET
IMPORTANT
For relays to use the Reset function of the con-
troller, both modulating outputs (MOD 1 and
MOD 2) must be set for Reset.
Relays that have Reset set to YES use the reset curve
configured for MOD 1.
1. Press the X button to display the Reset values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
If you select YES, then all other outputs display this
Setup option and will use the reset curve programmed
for the first output.
If you select NO, then No Reset is configured for that
output and all other subsequent outputs.
Fig. 55. Setup - Outputs - Relay - Reset Runtime.
1.3.4.3. RESET RT (run time)
This selection displays only if “Show RT = YES” is
selected during Output Options setup (see page 23).
1. Press the X button to display the Reset RT values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each individ-
ual relay. You must do this for each relay that
you want to reset to zero.
Fig. 56. Setup - Outputs - Relay - Exit.
1.3.4.4. EXIT Relay Setup
Press the W button to exit the selected relay set up and
return to the Outputs menu.
To setup the next relay output go to “1.3.4. Setting up the
Relays” on page 23.
When you finish setting up the relay outputs, continue
with “1.4. Exiting Setup”.
1.4. Exiting Setup
Press the HOME button to exit Setup mode and return to
the home screen display.
or
Use the S and T buttons to highlight EXIT from the menu
and press the X button.
This completes the Setup procedure.
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET
M24616
SETUP
OUTPUTS
RELAY 1
RESET RT
SETUP
OUTPUTS
RELAY 1
RESET RT
RESET
RUN TIME
FOR
RELAY 1
YES
NO
M24617
SETUP
OUTPUTS
RELAY 1
RESET
SCHEDULE
RESET RT
EXIT
M24618