Install Instructions

WIRING APPLICATION EXAMPLES T775U SERIES 2000 CONTROLLER
9 62-0255–03
Fig. 16. Wiring for mod motor or direct coupled
actuator with 0-10 Vdc control input.
Fig. 17. Wiring for Series 90 Modutrol Motor Control.
Fig. 18. Wiring for Changeover Relay and
Minimum Position Potentiometer used with
Series 90 Modutrol Motors.
T1 T2 C R
POWER
OUTPUT
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
1
HONEYWELL MODUTROL MOTOR WITH
VOLTAGE CONTROL INPUT
1
F
M24558A
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W
+
B
R
W
+
+
M24560A
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN
THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
1
2
3
MODULATING
OUTPUT
TERMINAL
(MOD 1)
B
R
W
+
B
R
W
+
T1 T2 B WR
POWER
OUTPUT
HONEYWELL ELECTRONIC
SERIES 90 MODUTROL MOTOR
1
2
3
M24561A
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
A 250 OHM RESISTOR PROVIDES 40% AUTHORITY WHEN
USING A 150 OHM MINIMUM POSITION POTENTIOMETER.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
1
2
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W
+
B
R
W
+
T1 T2 B WR
POWER
OUTPUT
2
HONEYWELL
ELECTRONIC SERIES 90
MODUTROL MOTOR
1
W R B
MINIMUM POSITION
POTENTIOMETER
(Q209)
SPDT CHANGEOVER
(H205 OR H705)
3
3