Submittal Sheet

SPECIFICATION DATA
31-00096-02
BACnet® Fixed Function Thermostat
FOR FAN COIL/HEAT PUMP/CONVENTIONAL SYSTEMS
APPLICATION
The BACnet Fixed Function (BACnet FF) thermostats are
configurable devices with 19 factory-loaded applications
for specific and common projects including fan coil, heat
pump and roof top equipment control.
The BACnet FF thermostats come in two models, the
standard TB3026B and the wireless enabled TB3026B-W.
Each model is a communicating, intelligent sensor-
controller combination with built-in temperature and
humidity sensors used to control the pre-loaded
applications. They provide a cost effective solution for
occupancy and crowd monitoring in hotel rooms,
conference rooms, schools, office buildings and more. The
large, easy-to-see display and easy-to-use interface
allows for the complexity of direct digital control (DDC) in
a user friendly package.
The BACnet FF thermostats communicate over an MS/TP
LAN so each device operates as a fully functioning BACnet
controller while easily integrating with the building
automation system. These devices are configured using
the Niagara Framework® software where a configuration
wizard will enable an intuitive setup.
FEATURES
19 pre-loaded applications for a quick, out-of-the-
box solution.
Optional integrated wireless receiver saves wiring
time and costs, provides more location options.
Internal temperature and humidity sensors, 3
universal inputs, 6 relay outputs, 2 analog outputs.
BACnet-compliant on MS/TP LAN at up to 76.8 Kbps
with an internal DDC logic loop of 100 msec.
A configurable device that is capable of stand-alone
or integrated operation.
Sleek sophisticated design with touch screen display
with dual setpoints.
DESCRIPTION
The BACnet FF thermostats are available in two models, as
described in Table 1.
Both thermostat models are configurable and come with
19 factory-loaded applications. The TB3026B-W includes
an integral wireless receiver providing compatibility with
wireless occupancy sensors.
Equipment Control Options
2-Pipe Fan Coil, 4-Pipe Fan Coil, Water/Air Source Heat
Pump, Roof Top Unit
On/Off, Three Speed or VFD Controlled Fan
Floating, Two-Position or Analog Cooling/Heating
Valve Control
On/Off Compressor and Heating Stages
Floating or Analog Economizer Control
Space, Outdoor or Supply Air Remote Sensors
Table 1. Thermostat Configurations.
Thermostat
Model
UI
(Universal
Input)
AO
(Analog
Output)
DO
(Relay
Output)
Integrated
Wireless
Receiver
TB3026B 3 2 6 NO
TB3026B-W 3 2 6 YES