Owner's Manual

Approved accessories as previously listed can be used to relocate or change the
type of antenna used.
5.3 Communication and Supervision Requirements
If using the TG-7FS LTE unit as the sole path of communication, it will be necessary
for the TG-7FS LTE unit to provide dial tone to both Telco connections on the panel,
unless one can be disabled. To do this, the Tip and Ring connection on the FACP
must be connected in parallel for both Telco connections.
As far as supervision of the TG-7FS, there are two System Trouble Condition relays
that can be used to locally annunciate to the panel of any issues, as programmed
during registration. However, the TG-7FS LTE will also announce through the
suppression of the dial tone to the panel of any issues caused by No Service or Radio
Failure conditions.
Note: Because a low/missing battery or low/missing AC power on the TG-7FS LTE
unit will not results in any other type of annunciation, at least one STC relay should
be connected to a zone on the FACP.
5.4 Other UL Installation Requirements
Household
Fire
Household
Burg/Fire
Combination
Commercial
Fire
Optional Optional Required AC transformer lines in flexible
conduit.
Required Required Required AC transformer plugged into un-
switched outlet.
Optional Optional Required AC transformer plugged into
dedicated branch circuit.
Optional Optional Optional Enclosure Tamper Switch
connected to 24-hour circuit.
Optional Optional Required Antenna cable in flexible conduit
concealed or covered by motion
detector.
firealarmresources.com