* If an EIM is used, or ISU 222 “Economizer fault FDD” is
set to “no” then the A-L/A is used for economizer control.
If ISU 222 “Economizer fault FDD” is set to “yes” then the
U1 contacts are used for economizer control.
Time of Day (TOD)
The thermostat can be set up for a Time of Day output in
the installer setup. This output is commonly used to control
lighting panels, turning them on for occupied periods and
off for unoccupied periods. Table 6 explains how the TOD
feature works with various thermostat modes.
* If an EIM is used, or ISU 222 “Economizer fault FDD” is
set to “no” then the A-L/A is used for TOD control. If ISU
222 “Economizer fault FDD” is set to “yes” then the U1
contacts are used for TOD control.
The Economizer Module and Time of Day output connect
to the A-L/A terminal at the thermostat or EIM and are set
up at ISU 222.
Fig. 296.
Pre-Occupancy Purge
The thermostat can be set up for Pre-Occupancy Purge in
the installer setup (ISU 401). When setup for Pre-
Occupancy Purge, the thermostat runs the fan 1 to 3 hours
before each occupied period to provide a comfortable
workplace upon arrival. Options are Off and 1 to 3 hours.
Table 5. Economizer Operation.
Thermostat Mode Equipment Operation
A-L/A
terminal or U1
Contacts*
Occupied Heat/Cool/Fan
running
A-L/A
energized or
U1 contacts
closed. *
Occupied
temporarily
Heat/Cool/Fan
running
Occupied Heat/Cool/Fan NOT
running
Occupied
temporarily
Heat/Cool/Fan NOT
running
Pre-occupancy
purge
Fan running
Unoccupied Cooling system
running
Unoccupied
temporarily
Cooling system
running
Standby Cooling system
running
Unoccupied Cooling system NOT
running
A-L/A NOT
energized or
U1 contacts
open. *
Unoccupied
temporarily
Cooling system NOT
running
Standby Cooling system NOT
running
A-L/A
energized or
U1 contacts
closed. *
Non-
programmable
Fan running
Non-
programmable
Fan NOT running A-L/A NOT
energized or
U1 contacts
open. *
Table 6. TOD Operation.
Thermostat Mode
Borne A-L/A
or U contacts*
Occupied A-L/A
energized or U
contacts
closed*
Occupied temporarily
Temperature overrides
Unoccupied
A-L/A NOT
energized or U
contacts open*
Unoccupied temporarily
Standby
Non-programmable