VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 108
* If an EIM is used, or ISU 222 “Economizer fault FDD” is
set to “no” then the A-L/A is used for economizer control.
If ISU 222 “Economizer fault FDD” is set to “yes” then the
U1 contacts are used for economizer control.
Time of Day (TOD)
The thermostat can be set up for a Time of Day output in
the installer setup. This output is commonly used to control
lighting panels, turning them on for occupied periods and
off for unoccupied periods. Table 6 explains how the TOD
feature works with various thermostat modes.
* If an EIM is used, or ISU 222 “Economizer fault FDD” is
set to “no” then the A-L/A is used for TOD control. If ISU
222 “Economizer fault FDD” is set to “yes” then the U1
contacts are used for TOD control.
The Economizer Module and Time of Day output connect
to the A-L/A terminal at the thermostat or EIM and are set
up at ISU 222.
Fig. 296.
Pre-Occupancy Purge
The thermostat can be set up for Pre-Occupancy Purge in
the installer setup (ISU 401). When setup for Pre-
Occupancy Purge, the thermostat runs the fan 1 to 3 hours
before each occupied period to provide a comfortable
workplace upon arrival. Options are Off and 1 to 3 hours.
Table 5. Economizer Operation.
Thermostat Mode Equipment Operation
A-L/A
terminal or U1
Contacts*
Occupied Heat/Cool/Fan
running
A-L/A
energized or
U1 contacts
closed. *
Occupied
temporarily
Heat/Cool/Fan
running
Occupied Heat/Cool/Fan NOT
running
Occupied
temporarily
Heat/Cool/Fan NOT
running
Pre-occupancy
purge
Fan running
Unoccupied Cooling system
running
Unoccupied
temporarily
Cooling system
running
Standby Cooling system
running
Unoccupied Cooling system NOT
running
A-L/A NOT
energized or
U1 contacts
open. *
Unoccupied
temporarily
Cooling system NOT
running
Standby Cooling system NOT
running
A-L/A
energized or
U1 contacts
closed. *
Non-
programmable
Fan running
Non-
programmable
Fan NOT running A-L/A NOT
energized or
U1 contacts
open. *
Table 6. TOD Operation.
Thermostat Mode
Borne A-L/A
or U contacts*
Occupied A-L/A
energized or U
contacts
closed*
Occupied temporarily
Temperature overrides
Unoccupied
A-L/A NOT
energized or U
contacts open*
Unoccupied temporarily
Standby
Non-programmable