VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
135 68-0312—05
Fig. 338. Connecting a stage of heating or cooling to a universal relay (U1, U2, U3).
1U1, U2, and U3 are normally open dry contacts when set up for a stage of heating or cooling.
2You must install a field jumper if the stage of heating or cooling is powered by the system transformer. Do NOT install a
field jumper if the stage of heating has its own transformer.
1
2
U3
U3
U2
U2
U1
U1
120
VAC
24
VAC
24
VAC
HEAT STAGE 3,
COOL STAGE 3,
COOL STAGE 4 OR
GEOTHERMAL
RADIANT HEAT
RH
RC
R
C
TRANSFORMER