VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 140
Wiring guide — Wired Indoor Sensors
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large
inductive loads such as motors, line starters,
lighting ballasts and large power distribution
panels.
Use shielded cable to reduce interference when
rerouting is not possible.
IMPORTANT
Erratic temperature readings from a sensor can
occur as a result of any of the wiring practices
described below. Avoid these practices to assure
correct operation. Use shielded cable to reduce
interference if rerouting sensor wiring is not possi-
ble.
— Be sure wires have a cable separate from the ther-
mostat cable.
— Do not route temperature sensor wiring with build-
ing power wiring, next to control contactors or near
light dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth
ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Use the S1, S2, S3 or S4 terminals for wired sensors.
Wiring 4 C7189U1005 sensors (10k ohm) for temperature
averaging network. Select 10K in the Installer Setup (ISU
503) when using C7189U1005 sensor(s).
Fig. 346. Wiring 4 C7189U sensors.
Wiring 2 TR21 sensors (20k ohm) and 1 TR21-A sensor
(10k ohm) for temperature averaging network. Select 20K
in the Installer Setup (ISU 503) when using 2 TR21 sensors
and 1 TR21-A sensor.
Fig. 347. Wiring 2 TR21 sensors and 1 TR21-A sensor.
Wiring 4 TR21 sensors (20k ohm). Select 20K in the
Installer Setup (ISU 503) when using TR21 sensor(s).
Fig. 348. Wiring 4 TR21 sensors.
Wiring 2 TR21-A sensors (10k ohm) for temperature
averaging network. Select 20K in the Installer Setup (ISU
503) when using 2 TR21-A sensors in series. Note: The
TR21-A sensor must be used in combination with TR21 or
TR21-A sensor.
Fig. 349. Wiring 2 TR21-A sensors.
C7189
C7189
C7189
C7189
EIM
M31472
THE NUMBER OF C7189U SENSORS MUST BE
A SQUARE NUMBER (1, 4, 9, 16, ETC.)
1
1
M31473
EIM
TR21-A
T3
T4
TR21 TR21
M31474
EIM
TR21 TR21
TR21 TR21
M31475
EIM
TR21-A
T3
T4
TR21-A
T3
T4