Zoning and Ventilation
Fig. 352. RedLINK VisionPRO thermostat with an HZ432 zone panel and a ventilator.
Setting up Ventilation Control on RedLINK VisionPRO Thermostats
Select the terminals wired to the ventilator at ISU 1002 (U1, U2, U3). In Fig. 352, the ventilator is wired to U1. To ventilate in
all zones, set ISU 1006 Vent Fan Control to “Equip Controls Fan.
TrueDRY dehumidifier with Zoning
Fig. 353. RedLINK VisionPRO thermostat with an HZ432 zone panel and a TrueDRY dehumidifier.
Setting up Dehumidification Control on RedLINK VisionPRO Thermostats
Select the terminals wired to the dehumidifier at ISU 904 (U1, U2, U3). In Fig. 353, the dehumidifier is wired to U1. To
dehumidify in all zones, set ISU 913 Dehum Fan Control to “Equip Controls Fan.
RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK
M34529
EQUIPMENT
C
R
W
Y
G
FURNACE
TrueZONE PANEL
VisionPRO
EIM
ERV/HRV
INTERLOCK B G R
AUX W B G R
2
2
1
1
SELECT THE TERMINALS WIRED TO THE VENTILATOR AT ISU 1002
(U1, U2, U3). TO VENTILATE IN ALL ZONES, SET ISU 1006 VENT FAN
CONTROL TO EQUIP CONTROLS FAN.
FOR ALL ZONE PANEL WIRING NOT SHOWN IN THIS DIAGRAM, SEE
OTHER ZONING DIAGRAMS OR ZONE PANEL INSTALLATION
INSTRUCTIONS.
RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK
EQUIPMENT
C
R
W
Y
G
FURNACE
TrueZONE PANEL
VisionPRO
EIM
TrueDRY DEHUMIDIFIER
DHUM R FAN C GT Rf Gf
2
2
1
1
SELECT THE TERMINALS WIRED TO THE VENTILATOR AT ISU 904 (U1, U2, U3).
TO VENTILATE IN ALL ZONES, SET ISU 913 DEHUM FAN CONTROL TO EQUIP
CONTROLS FAN.
FOR ALL ZONE PANEL WIRING NOT SHOWN IN THIS DIAGRAM, SEE OTHER
ZONING DIAGRAMS OR ZONE PANEL INSTALLATION INSTRUCTIONS.
M34530