VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
15 68-0312—05
TrueSTEAM
1. Wire and power TrueSTEAM.
2. Connect the ABCD terminals between TrueSTEAM
and the THM4000 Wireless Adapter.
3. Adjust the DIP Switches on TrueSTEAM as follows
when using the Wireless Adapter:
•DIP3: UP
•DIP4: UP
•DIP5: DOWN
Fig. 27. Powering TrueSTEAM wireless adapter.
Entry/Exit Remote or Vent Boost Remote
1. Remove the cover.
2. Insert the CR2450 coin cell battery (included) into
the slot at the bottom of the remote. See polarity
marking on the remote.
Fig. 28. Installing Entry/Exit Remote or Vent Boost
Remote battery.
3. The LED will briefly flash green. If it flashes red, bat-
tery is not good.
PERFORMING INITIAL SETUP
NOTE: If the thermostat is wired directly to the equip-
ment, 24 VAC (C wire) is required to connect
RedLINK accessories. Turn on 24 VAC before per-
forming the initial setup.
Initial setup options define the type of system you are
installing:
• Residential or commercial
• Non-zoned or zoned
• Used with or without an Equipment Interface Module
(THM5421)
• Used with or without the TrueZONE Wireless Adapter
(THM4000)
1. Follow prompts on the screen to select the appropri-
ate options.
Fig. 29. Select application (residential or commercial).
NOTE: If you are connecting the thermostat to the True-
ZONE Wireless Adapter (THM4000), refer to the
TrueZONE instructions to link the thermostat and
RedLINK accessories.
Linking Thermostat to Equipment
Interface Module (if used)
1. In thermostat setup, when you are prompted to
answer TSTAT CONTROLS AN EQUIP. MODULE:
select yes, then press Next.
Fig. 30.
2. Press and quickly release the CONNECT button on
the EIM. Make sure the “Connected” light is flashing
green.
Fig. 31. EIM CONNECT button.
NOTE: If the “Connected” light does NOT flash
green, another system may be in the listen-
ing mode. Please exit the listening mode at
the other system and then try again.
Green Flashing: In Listening Mode - system
is ready to add RedLINK devices.
Green Steady: RedLINK devices are commu-
nicating.
Red: RedLINK device(s) are NOT communi-
cating. Check EIM and RedLINK devices.
THM4000R1000
TrueSTEAM
MCR31476
6
543
2
ON
OFF
1
MCR33269
APPLICATION
residential
CONNECT
CONNECTED