VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 22
Fig. 62.
4. Select Installer Setup.
Fig. 63.
5. Follow prompts on the screen to select the desired
setup options. See Table 2 for Installer Setup options.
MCR33977
Enter password
0 0 0 0
MCR34015
Installer Setup
Installer Test
Table 2. Installer Setup (ISU) Table.
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
101 Application
Residential
Commercial
Residential Both No
102 Zone Number
1-16
1 Both No This ISU is only displayed on a thermostat that is
controlling a zone panel through the THM4000
Wireless.
103 Thermostat Name
[Select Thermostat Name]
Thermostat Both No The Portable Comfort Control remote and Web
Interface displays the name of the thermostat that
you enter on this screen.
104 Thermostat Type
Non-Programmable
Programmable
Programmable Both No
105 Temperature Scale
Fahrenheit
Celsius
Fahrenheit Both No
106 Outdoor Air Sensor
No
Yes
No Both No This ISU automatically defaults to Yes when a
Wireless Outdoor Sensor is connected.
An Outdoor Sensor is required to set the following
ISUs:
ISU 312 Outdoor Temperature Lockouts (Heat
Pump Lockout and Backup Heat Lockout)
ISU 405 Outdoor Temperature used with
Minimum Heat Recovery Ramp Rate
ISU 406 Outdoor Temperature used with
Maximum Heat Recovery Ramp Rate
ISU 407 Outdoor Temperature used with
Minimum Cool Recovery Ramp Rate
ISU 408 Outdoor Temperature used with
Maximum Cool Recovery Ramp Rate
ISU 805 Humidification - Window Protection
ISU 1013 Low Outdoor Temperature Ventilation
Lockout
ISU 1013 High Outdoor Temperature Ventilation
Lockout
ISU 1013 High Outdoor Dew Point Ventilation
Lockout (requires Wireless Outdoor Sensor)
200 Heating System
Conv. Forced Air
Heat Pump
Radiant Heat
Other
None (Cool Only)
Conv. Forced Air Both No