VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
27 68-0312—05
300 System Changeover
Manual
Automatic
Manual:
if ISU 101 is
Residential
Automatic:
if ISU 101 is
Commercial
Both No Manual: The user must select heating or cooling as
needed to maintain the desired indoor
temperature.
Automatic: The user has the option to select Auto
for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.
300 Auto Changeover
Deadband
2° F to 9° F (in 1° F increments)
3° F Both No This ISU is only displayed when ISU 300 is set to
Automatic.
Deadband is the minimum separation between
heat and cool settings when the thermostat is
setup for Auto Changeover. For example, if the
deadband is set to 3° F and the cool setpoint is 75°
F, the warmest heat setpoint allowed would be 72°
F. If the heat setpoint is adjusted above 72° F, it
will automatically adjust the cooling setpoint
higher to maintain the 3° F deadband.
When ISU 907 or ISU 910 (Dehum Over Cooling
Limit) is set to 1, 2, 3, 4 or 5 F, the thermostat will
not show the full Deadband range. For example, if
you set a Deadband of 3 F and an Over Cooling
Limit of 2 F, the minimum Deadband that you can
select will be 5 F. This prevents the heating system
from turning on when the thermostat over cools to
reach the dehumidification setting.
301 Control Options
Basic Options
Advanced Options
Basic Options Both No Basic Options: The Installer Setup displays basic
temperature control options which include Backup
Heat Droop, Backup Heat Upstage Timer, Outdoor
Temperature Lockouts and Cycle Rate settings per
stage.
Note: Outdoor Temperature Lockouts only apply to
Heat Pump applications.
Advanced Options: The Installer Setup displays
both Basic and Advanced Options. Advanced
temperature control options include Finish With
High Cool Stage, Finish With High Heat Stage, and
Temperature Differential settings between all
stages.
302 Finish With High
Cool Stage
No
Yes
No Both No ISU 301 Control Options must be set to Advanced
to view or adjust Finish With High Cool Stage.
This ISU is only displayed when the thermostat is
set for 2 or more cool stages.
When set to Yes, this feature keeps the high stage
of the cooling equipment running until the desired
setpoint is reached.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes