VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
29 68-0312—05
304 Radiant Heat Diff.
Stage 2
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and there are 2
radiant heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 2 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
305 Heat Differential
Stage 2
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 2 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 2 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
305 Heat Differential
Stage 3
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301Temperature Control Options must be set
to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional systems
that have 3 heat stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 3 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 3 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
306 Compressor Heat
Diff. Stage 1
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and ISU 205
Geo Forced Air is set to Heating and Cooling.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 1 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 1 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes