VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 30
306 Compressor Heat
Diff. Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Air to Air Heat Pump, Geothermal or
Geothermal Radiant and there are 2 compressor
stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 2 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
308,
309
Backup Heat Droop
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1 stage
of Backup Heat.
Comfort
2.0° F to 15.0° F from setpoint (in
0.5° F increments)
Comfort Both No A backup heat droop can be set on any system that
has more than one heating equipment type.
See “Backup Heat Droop” beginning on page 76.
The Comfort setting is NOT available for Dual Fuel
systems. For example, Heat Pumps with Gas
Forced Air.
308,
309
Backup Heat Droop
Stage 2
Comfort
2.0° F to 15.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust Backup Heat Droop Stage 2.
This ISU is only displayed if there are 2 backup
heat stages.
The indoor temperature must drop to the selected
droop setting before the thermostat will turn on
backup heat stage 2. For example, if backup heat
stage 2 is set to 2° F (1.0° C), the indoor
temperature must be 2° F (1.0° C) away from the
setpoint before backup heat stage 2 turns on.
When set to Comfort, the thermostat will use
backup heat stage 2 as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
311 Upstage Timer for
Backup Heat
Off
(30, 45, 60, 75, 90) minutes
(2, 3, 4, 5, 6, 8, 10, 12, 14, 16)
hours
Off Both No The Backup Heat Upstage Timer starts when the
highest stage of the previous heating equipment
type turns on. Backup heat will be used (if needed)
when the timer expires. See “Backup Heat Upstage
Timer” beginning on page 77.
This ISU is only displayed when Backup Heat
Droop Stage 1 is set to 2 F or higher (ISU 308,
309).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes