VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 30
306 Compressor Heat
Diff. Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Air to Air Heat Pump, Geothermal or
Geothermal Radiant and there are 2 compressor
stages.
The indoor temperature must drop to the selected
differential setting before the thermostat will turn
on the stage of heating. For example, if stage 2 is
set to 2° F (1.0° C), the indoor temperature must
be 2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as needed
to keep the indoor temperature within 1° F (0.5°
C) degree of the setpoint.
308,
309
Backup Heat Droop
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1 stage
of Backup Heat.
Comfort
2.0° F to 15.0° F from setpoint (in
0.5° F increments)
Comfort Both No A backup heat droop can be set on any system that
has more than one heating equipment type.
See “Backup Heat Droop” beginning on page 76.
The Comfort setting is NOT available for Dual Fuel
systems. For example, Heat Pumps with Gas
Forced Air.
308,
309
Backup Heat Droop
Stage 2
Comfort
2.0° F to 15.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to Advanced
to view or adjust Backup Heat Droop Stage 2.
This ISU is only displayed if there are 2 backup
heat stages.
The indoor temperature must drop to the selected
droop setting before the thermostat will turn on
backup heat stage 2. For example, if backup heat
stage 2 is set to 2° F (1.0° C), the indoor
temperature must be 2° F (1.0° C) away from the
setpoint before backup heat stage 2 turns on.
When set to Comfort, the thermostat will use
backup heat stage 2 as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
311 Upstage Timer for
Backup Heat
Off
(30, 45, 60, 75, 90) minutes
(2, 3, 4, 5, 6, 8, 10, 12, 14, 16)
hours
Off Both No The Backup Heat Upstage Timer starts when the
highest stage of the previous heating equipment
type turns on. Backup heat will be used (if needed)
when the timer expires. See “Backup Heat Upstage
Timer” beginning on page 77.
This ISU is only displayed when Backup Heat
Droop Stage 1 is set to 2 F or higher (ISU 308,
309).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes