VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 36
402 Type of Override
Standard
Initiate Occupancy
Standard Commercial No Standard:
The system maintains temperatures
programmed for the occupied and
unoccupied time periods. Pressing
OVERRIDE will allow the user to make a
temporary schedule change.
Initiate Occupancy:
The system maintains temperature at an
energy saving level until the user touches the
message center area on the thermostat. Note:
The message center displays Press HERE to
Start Occupancy. The system will then
maintain a comfortable temperature until the
occupied period ends. This option is
recommended for cost savings when the
workplace is used infrequently or arrival
times change from day to day (example -
schools). After the user touches Press HERE
to Start Occupancy, the user will still be
able to perform a standard OVERRIDE of
the schedule.
403 Override Duration
No Limit
1 to 12 Hours
3 hours Commercial No When the user presses the OVERRIDE button, the
thermostat will maintain the new temperature for
at least 1 hour. The user can adjust the Hold Until
time from 1 hour to the amount set for the
Override Duration (1-12 hours). Default setting is
3 hours. If set to No Limit, the user can adjust the
Hold Until time up to 24 hours.
405 Min. Heat Recovery
Ramp Rate
Off
1° F/hr to 20° F/hr
5° F/hr Commercial No Off: The heating system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the heating system can recover at for a
cold day in your region. Default setting is 5° F /
hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day in
your region to be associated with the Minimum
Recovery Ramp Rate. The thermostat will begin
recovery at the optimal time based on a calculated
ramp rate, allowing the system to recover on time
and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes