VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 40
408 Max. Cool Recovery
Outdoor Temp
Off
-20° F to 100°F
70° F Commercial No Off: The cooling system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a
mild day in your region. Default setting is 6° F /
hour.
Set an Outdoor Temperature that is representative
of a mild day in your region to be associated with
the Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
409 Adaptive Recovery
No
Yes
Yes Residential No No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or cooling
recovery early to ensure that the temperature is
reached at the scheduled time. The thermostat will
adjust the start time of the equipment based on
how quickly the scheduled temperature was
reached on previous days. See page 71 for more
information on Adaptive Intelligent Recovery.
410 Minimum Cool
Setpoint
50° F to 99° F
50° F Both No The user cannot set the temperature below this
level.
410 Maximum Heat
Setpoint
40° F to 90° F
90° F Both No The user cannot set the temperature above this
level.
411 Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked Both No Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any settings.
412 Residential:
Entry / Exit Remote
- Home Cool
Setpoint
Commercial:
Entry / Exit Remote
- Occupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
75° F Both No The thermostat maintains this Cool setting when
the user presses Home / Occupied at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes