VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
41 68-0312—05
412 Residential:
Entry / Exit Remote
- Home Heat
Setpoint
Commercial:
Entry / Exit Remote
- Occupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
70° F Both No The thermostat maintains this Heat setting when
the user presses Home / Occupied at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
413 Residential:
Entry / Exit Remote
- Away Cool
Setpoint
Commercial:
Entry / Exit Remote
- Unoccupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
78° F Both No The thermostat maintains this Cool setting when
the user presses Away / Unoccupied at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
413 Residential:
Entry / Exit Remote
- Away Heat
Setpoint
Commercial:
Entry / Exit Remote
- Unoccupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
65° F Both No The thermostat maintains this Heat setting when
the user presses Away / Unoccupied at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
414 Residential:
Entry / Exit Remote
- Vacation Cool
Setpoint
Commercial:
Entry / Exit Remote
- Holiday Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
82° F Both No The thermostat maintains this Cool setting when
the user presses Vacation / Holiday at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
414 Residential:
Entry / Exit Remote
- Vacation Heat
Setpoint
Commercial:
Entry / Exit Remote
- Holiday Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
60° F Both No The thermostat maintains this Heat setting when
the user presses Vacation / Holiday at the Entry /
Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See “Wireless
Entry/Exit Remote” beginning on page 112.
500 Wired Sensor on S
Terminals
No
Yes
No Both No This ISU is only displayed if an S1–S4 terminal is
available.
500 Wired Remote
Indoor Sensor
No
Yes
No Both No The thermostat will not display the Wired Remote
Indoor Sensor option if 6 wireless indoor air
sensors are already connected to the thermostat. If
you have a wired Indoor Air Temperature network
(1, 4, 9 etc), the thermostat will allow up to 5
wireless indoor air sensors.
500 Wired Outdoor
Sensor
No
Yes
No Both No The thermostat will not display the Wired Outdoor
Sensor option if a wireless outdoor air sensor is
already connected to the thermostat.
500 Wired Return
Sensor
No
Yes
No Both Yes The thermostat will not display the Wired Return
Sensor option if there is no fan in the system.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes