VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 42
500 Wired Discharge
Sensor
No
Yes
No Both No The thermostat will not display the Wired
Discharge Sensor option if there is no fan in the
system.
501 Indoor Sensor
Name
[Select Indoor Sensor Name]
Indoor Sensor Both No Select a name (location) of the Wired Remote
Indoor Sensor.
502 Indoor Sensor
None
S1
S2
S3
S4
None Both No Select the terminals wired to the Remote Indoor
Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
503 Indoor Sensor Type
10K
20K
10K:
if ISU 101
Application is
Residential
20K:
if ISU 101:
Application is
Commercial
Both No Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21 sensor
or another TR21-A sensor for the thermostat to
calculate the correct indoor temperature reading).
See “Wiring guide — Wired Indoor Sensors”
beginning on page 140 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would select
20K when you have two TR21-A (10K) sensors
wired in series.
504
Use [T-Stat Sensor]
for Temp Ctrl
Use [Remote Indoor
Sensor Name] for
Temp Ctrl
Use [T-Stat Sensor]
in Temp Avg
Use [Remote Indoor
Sensor Name] in
Temp Avg
Use T-Stat Sensor for Temp Ctrl -
Yes or No
Use [Remote Indoor Sensor
Name] for Temp Ctrl - Yes or No
Use T-Stat Sensor in Temp Avg -
Yes or No
Use [Remote Indoor Sensor
Name] in Temp Avg - Yes or No
(Up to 6 Remote Indoor Sensors)
Sensors are
Averaged (T-Stat
Sensor and
Remote)
Both No Select the sensors to be used for temperature
control. If you select more than one, the
thermostat will average the temperature readings
from each sensor.
See “Remote Indoor Sensors” beginning on
page 115.
505 Outdoor Sensor
None
S1
S2
S3
S4
None Both No Select the terminals wired to the Outdoor Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
507 Return Sensor
None
S1
S2
S3
S4
None Both Yes Select the terminals wired to the Return Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
508 Return Sensor Type
10K
20K
10K Both Yes Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes