509 Discharge Sensor
None
S1
S2
S3
S4
None Both No Select the terminals wired to the Discharge Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
510 Discharge Sensor
Type
10K
20K
10K Both No Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
511 A-Coil Low Temp.
Cutoff
Off
35° F to 65° F (in 5° F
increments)
Off Both No If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a
safe level.
600 Dry Contact Device
on S Terminals
No
Yes
No Both Yes Dry Contact Alerts and Remote Setback require an
Equipment Interface Module. This ISU is only
displayed if an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on page 74
and “Remote Setback (Commercial Use)”
beginning on page 106.
600 Remote Setback Dry
Contact
No
Yes
No Commercial Yes Remote Setback requires an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
600 Full Drain Pan Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
600 Dirty Filter Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
600 Water Leak Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
600 Sys. Shutdown Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
600 Service Needed Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes