600 Fan Failure Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
600 Custom Dry Contact
Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See “Dry Contact Alerts” beginning on page 74.
601 Remote Setback
None
S1
S2
S3
S4
None Commercial Yes Remote Setback requires an Equipment Interface
Module.
Select the terminals wired to the Remote Setback
Dry Contact Device.
602 Remote Setback is
[See Settings]
N.O. when Occupied
N.C. when Occupied
N.O. when
Occupied
Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open when Occupied: The Dry Contact
device is open when the room is occupied and will
close when the room is unoccupied.
Normally Closed when Occupied: The Dry Contact
device is closed when the room is occupied and will
open when the room is unoccupied.
603 Remote Setback
Time Delay
0 to 30 minutes (in 5 minute
increments)
0 minutes Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
The Remote Setback Time Delay forces the
thermostat to wait before it switches from
Occupied to the Remote Setback temperature
settings.
When set to 0 minutes, the thermostat will switch
from Occupied to the Remote Setback
temperature settings immediately when the room
is unoccupied.
604 Remote Setback
Cool Setpoint
72° F to 90° F
85° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to setback settings when
no one is in the room. If someone is in the room,
then it follows the settings of the occupied period.
The occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
setback settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.