VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
47 68-0312—05
616 Fan Failure Alert is
[See Settings]
N.O. when Fan Runs
N.C. when Fan Runs
N.C. when Fan
Runs
Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open when Fan is Running: The Dry
Contact device is open when the fan is running
and will close when the fan is not running.
Normally Closed when Fan is Running: The Dry
Contact device is closed when the fan is running
and will open when the fan is not running.
617 Custom Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Custom Dry
Contact Device.
618 Custom Alert is [See
Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
619 Custom Alert Name
View/Edit Custom Alert
View/Edit
Custom Alert
Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Enter a name for the custom alert dry contact. The
thermostat displays this name including a brief
message (entered on the next screen - ISU 620)
when a dry contact device detects a problem.
620 Cust Alert Message
View/Edit Custom Alert
View/Edit
Custom Alert
Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Enter a message for the custom alert dry contact.
The thermostat displays this message when a dry
contact device detects a problem.
700 Filter Type
None
Elec. Air Cleaner
Media
Media Both No
702 Number of Air
Filters
1 to 2
1BothNo
711 Air Filter 1
Reminder
Note: “1” is not
displayed if there is
only 1 filter.
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both No
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes