8000 WITH REDLINK™
91 68-0312—05
4. Select the terminals wired to the Dehumidifier. See
Fig. 219.
Fig. 219.
5. Select the system mode(s) to allow dehumidification.
See Fig. 220.
NOTE: Heat includes Heat, Emergency Heat and
Auto. If the system is in Auto mode, the ther-
mostat will allow dehumidification if the last
call was for heat.
Cool includes Cool and Auto. If the system is
in Auto mode, the thermostat will allow
dehumidification if the last call was for cool.
Fig. 220.
6. Set Dehumidifier Fan Control settings. See Fig. 221.
Tstat Controls Fan
Thermostat turns on the dehumidifier and the fan
when dehumidification is needed.
Equip Controls Fan
Thermostat turns on the dehumidifier when
dehumidification is needed. The fan is controlled
by the equipment.
Fig. 221.
7. Set the desired lockout option. See Fig. 222.