VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 52
919 Dehum Away Mode
Fan Setting
Automatic
On
Circulate
Automatic Both No The On and Circulate settings may re-introduce
humidity into the living space.
920 Dehum Away Mode
Low Limit Temp
70° F to 80° F
76° F Both No If the cooling system is used to control humidity
while Dehumidification Away Mode is active, the
thermostat allows the cooling system to lower the
indoor air to the Low Limit Temperature Setting to
reach the dehumidification setting at ISU 920.
920 Dehum Away mode
Temp Setting
70° F to 99° F
85° F Both No The temperature maintained while
Dehumidification Away Mode is active and the
desired humidity level is satisfied.
920 Dehum Away mode
Dehum Setting
40% to 70% (in 5% increments)
65% Both No The desired humidity level while Dehumidification
Away Mode is active.
921 Dehumidifier Filter
Reminder
Off
30, 60, Calendar Days
3 to 12 Calendar Months (in 1
month increments)
Off Both No
1000 Ventilation Type
None
ERV / HRV
Passive (Fan Only)
Fresh Air Damper
None Both No None: The thermostat does not control ventilation.
ERV/HRV: The thermostat controls an Energy
Recovery Ventilator or Heat Recovery Ventilator
for ventilation.
Passive (Fan Only): The thermostat turns on the
fan for ventilation.
Fresh Air Damper: The thermostat turns on the fan
and opens a fresh air damper for ventilation.
1002 Ventilation Wiring
None
U1
U2
U3
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Both No Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2 and
U3 terminals
U1, U2, U3 are dry contacts that require power.
See “Wiring IAQ Equipment or a Heat/Cool Stage
to the Universal Terminals” beginning on
page 133.
1005 Ventilation Method
ASHRAE
Percent On Time
Defaults to
ASHRAE
when ISU 101
Application is set
to Residential.
Percent on Time
is the only
choice when ISU
101 Application
is set to
Commercial.
Both No See “Ventilation Control Methods (ISU 1005)”
beginning on page 92.
1006 Vent Fan Control
Tstat Controls Fan
Equip Controls Fan
Tstat Controls
Fan
Both No Tstat Controls Fan: The thermostat turns on the
ventilation equipment and the fan when
ventilation is needed.
Equip Controls Fan: The thermostat turns on the
ventilation equipment when ventilation is needed.
The fan is controlled by the equipment.
1009 Number of
Bedrooms
1 to 6
2 bedrooms Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes