VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
53 68-0312—05
1009 Size of House
1000 to 5000 sq. ft. (in 100 sq. ft.
increments)
(90 to 460 sq. m.)
1000 sq. feet Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
1010 Ventilation Rate
30 to 350 CFM (in 5 CFM
increments)
(850 - 9900 LPM)
150 Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE (Residential
only).
1012 Vent Percent On
Time
10% to 100% (in 10%
increments)
30% Both No The thermostat operates ventilation equipment
based on a percentage entered in the installer
setup (ISU 1012). For example, if Percent on Time
is set to 50%, the ventilation equipment will run at
random times during a 1 hour period until it
reaches a 50% run time (approximately 30
minutes).
1012 Vent Priority
Lockouts
ASHRAE
Lockouts Residential No Lockouts are Priority: The thermostat places a
priority on lockouts versus the ASHRAE 62.2
ventilation standard. The thermostat will not run
ventilation during the following lockout conditions
(if configured) unless you manually call for
ventilation:
•
Lockout Ventilation during Outdoor
Conditions (ISU 1013)
• Lockout Ventilation on Humidification or
Dehumidification Calls (ISU 1014)
• Lockout Ventilation during “Sleep”
(Residential) or “Unoccupied” (Commercial)
program periods. Note: This option is set by
the user on the Ventilation screen in the Menu.
ASHRAE is Priority: ASHRAE requires additional
ventilation following a long off cycle. The
thermostat meets the ASHRAE 62.2 ventilation
standard by running additional ventilation when
outdoor conditions are favorable. If ASHRAE
cannot be met when outdoor conditions are
favorable, the thermostat will override the outdoor
lockouts and run ventilation. When using this
option, it is recommended to increase the rate
(CFM) of the ventilation equipment to meet the
ASHRAE 62.2 ventilation standard in a shorter run
time.
Notes:
•
ISU 1014 Lockout Ventilation on
Humidification or Dehumidification calls is not
an option when you select ASHRAE is
Priority.
• The ability to lockout ventilation during the
“Sleep” or Unoccupied program periods is not
an option when you select ASHRAE is
Priority.
1013 Low Outdoor Temp
Vent Lockout
Off
-20° F to 40° F (in 5° F
increments)
Off Both No Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh Air
Damper.
See “Ventilation — Outdoor Condition Lockouts
(ISU 1013)” beginning on page 93.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes