VisionPRO® 8000 Thermostats INSTALLER SETUP AND SYSTEM TEST POCKET GUIDE 62-0266-01
INSTALLER SETUP 1. Press SYSTEM. FAN ON Inside AUTO SYSTEM HEAT AM SCHED HOLD M24079 2. Press and hold these two blank buttons until the display changes.
. Use arrows to change settings as required. SETTING FUNCTION DONE PRESS TO SELECT FUNCTION PRESS TO CHANGE SETTING M24082A 4. Press DONE to exit and save settings. INSTALLER SETUP FUNCTIONS Available option and default settings vary by thermostat. Table 1. Installer Setup .
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0170 System Selection 8 1—1H/1C Conv 2—1H/1C HP 3—1H w/o fan 4—1H with fan 6—1C 7—2H/1C HP 8—2H/2C Conv 9—2H/1C Conv 10—1H/2C Conv 11—2H/2C HP 12—3H/2C HP 0175 TOD/ Economizer output (terminal A) 0 0—Unused 1—TOD 2—Economizer Economizer energizes A during a call for cool. TOD energizes A during Occupied period, and de-energizes A during Unoccupied.
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name 0230 CPH for second stage compressor 0240 Default Setting 3 All Settings Notes 1-6 Only shown if two stages of cool selected. CPH for first 5 stage conventional heat 1-12 Only shown if system is conventional with heat stages. Selection in this stage changes default CPH of second stage heat.
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0320 Temperature 0 Indication Scale 0—° F 1—° C 0330 Daylight Saving 2 0—Disabled 1—Enabled (US 1987) 2—Enable (US 2007) 3—Enabled (Europe) 0340 Remote 0 Temperature Sensor 0—None 1—Outdoor for Display 2—Outdoor for Control 3—Remote 10K Indoor 4—Remote 20K Indoor Averaging would not include onboard sensor. It is accomplished by series/parallel combinations.
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0535 Temporary Occupied Duration Limit 3 0—no duration 1—one hour 2—two hours 3—three hours 4—four hours 0 means no limit 0540 Number of Periods 4 2—2 Periods 4—4 Periods Does not appear if Non-programmable is chosen. Applies to all days of the week. With 2 selected the “Cancel Period” option does not appear on the display.
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0670 Keypad Lockout 0 0—Unlocked 1—Partial Lockout 1 2—Partial Lockout 2 3—Fully Locked Unlocked: All functions accessible. Partial 1: Locks all but Holiday, Override, and Up/ Down. Partial 2: Locks all but Holiday and Override. Full: Entire interface locked/ non-functional.
Table 1. Installer Setup (Continued). Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0690 Temperature 2 Control Cool 1—Less Aggressive 2—Standard 3—More Aggressive Only shown if system has cool stages. Only integral gains affected. Affects control operation in all control regimes (not just recovery or setpoint change). More Aggressive stops signal prior to reaching the setpoint. (For use with oversized equipment.
INSTALLER SYSTEM TEST The installer Test is part of the Installer Setup Menu. 1. Enter the installer System Test by entering the Installer Setup and pressing repeatedly until “Test” appears. DONE M24083 2. Use arrow to change test and system status as required. TEST NUMBER SYSTEM STATUS DONE PRESS TO SELECT TEST PRESS TO CHANGE STATUS M24085 3. Press DONE to exit.
SYSTEM TESTS Test the system’s heating cooling, fan and emergency heat. Available tests vary by thermostat and system type. Table 2. Installer System Tests.