Manual

T10 PRO SMART THERMOSTAT WITH REDLINK
21 33-00462—01
3150 Heat Cycles Per
Hour Stage 1
1-12 Default varies
based on
heating
equipment type
selected
This ISU is only displayed when ISU 2000 is
not seat for heat pump and ISU 2070 Heat
Stages is set to 1 or 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times per
hour (10 minutes on, 10 minutes off). The
system cycles less often when load
conditions are less than or greater than a
50% load. The thermostat automatically
defaults to the recommended cycle rate
based on the heating equipment type that is
used. You can change the cycle rate as
needed. Defaults for commonly used
systems are shown below.
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Steam = 1 CPH
3150 Heat Cycles Per
Hour Stage 2
1-12 Default varies
based on
heating
equipment type
selected
This ISU is only displayed when ISU 2071
Heat stages is set to 2 stage for
conventional forced air systems.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load for the
active stage.
3160 Backup Heat
Cycles per Hour
1-12 Default varies
based on
backup heating
equipment type
selected
This ISU is only displayed when ISU 2000 is
set for heat pump and ISU 2071 is set for 1
aux heat stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load for the
active stage.
3165 Emergency
Heat Cycles per
Hour
1-12 Default varies
based on
backup heating
equipment type
selected
This ISU is only displayed when ISU 2175
Aux/E terminal control is set for “Aux and E
Independent”.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times per
hour (10 minutes on, 10 minutes off). The
system cycles less often when load
conditions are less than or greater than a
50% load. The thermostat automatically
defaults to the recommended cycle rate
based on the heating equipment type that is
used. You can change the cycle rate as
needed. Defaults for commonly used
emergency heat shown below.
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Electric Forced Air = 9 CPH
Table 5. Installer Setup (ISU)
ISU #
Installer Setup
Name Settings Default Notes