Manual

T10 PRO SMART THERMOSTAT WITH REDLINK
23 33-00462—01
4110 Keypad Lockout Unlocked
Partially locked
Fully locked
Unlocked Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any
settings
5000 Is an indoor
sensor WIRED
to your System?
Indoor air temperature Unchecked box
(no indoor
sensor used)
Select this if a wired indoor sensor is
connected to the S terminals.
Outdoor wired sensor can be selected at the
ISU prior to 2000 for “outdoor temperature”.
* You cannot use both a wired outdoor and
wired indoor sensor, so if “outdoor
temperature” is set to wired sensor, ISU
5000 will not be shown.
5030 Indoor
temperature
sensor type
10K
20K
10K Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
C7189U1005 = 10K ohm
See “Installing Wired Indoor Sensor” on
page 14 for information wiring multiple
indoor sensors.
5040 Which Sensors
will be used for
Temperature
Control?
(Multiple
sensors are
averaged)
Thermostat
Remote Sensor
Both Select whether the internal thermostat
sensor or wired sensor(s) are used. If both
thermostat and remote sensor are selected,
the thermostat would count for 50% of the
average and all wired sensors combined
would count for the other 50% of the
average.
This setting does not pertain to the Wireless
indoor sensors. You can select which of
those are used for control temperature
under Menu-Priority from the home screen.
See “Installing Wired Indoor Sensor” on
page 15 for information wiring multiple
indoor sensors.
7000 Filter Type None
Media
None
7020 Number of air
filters
0-2 1 Only shown if ISU 7000 is set to media
7110 Air filter 1
replacement
reminder
Off
Run Time:
10, 20, 30 45, 60, 90,
120, 150 days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15
months
Off Only shown if ISU 7020 is set to 1 or 2
7110 Air filter 2
replacement
reminder
Off
Run Time:
10, 20, 30 45, 60, 90,
120, 150 days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15
months
Off Only shown if ISU 7020 is set to 2
8000 What type of
humidifier do
you have?
None
Steam
Bypass or fan
powered
None
Table 5. Installer Setup (ISU)
ISU #
Installer Setup
Name Settings Default Notes