Manual

T10 PRO SMART THERMOSTAT WITH REDLINK
33-00462—01 26
9210 Dehumidifi-
cation Filter
Replacement
Reminder
Off, 30, 60, Calendar
Days 3 to 12 Calendar
Months (in 1 month
increments)
Off
10000 Ventilation
Type
None
ERV/HRV
Passive (Fan Only)
Fresh Air Damper
None None: The thermostat does not control
ventilation.
ERV/HRV: The thermostat controls an
Energy Recovery Ventilator or Heat
Recovery Ventilator for ventilation.
Passive (Fan Only): The thermostat only
turns on the fan for ventilation. This
assumes the system has a damper that
automatically opens whenever the fan runs.
Fresh Air Damper: The thermostat turns on
the fan and opens a fresh air damper for
ventilation.
10050 Ventilation
Control Method
ASHRAE
Percent on Time
Ashrae See “Ventilation Control Methods (ISU
10050)” on page 35.
10060 Ventilation Fan
Control
Thermostat
Controls Fan
Equipment Controls
Fan
if “fresh air damper” or
“passive” is selected for
ISU 10,000. This
setting is not shown
and thermostat
controls fan by default
Thermostat
Controls Fan
Thermostat Controls Fan: The thermostat
turns on the ventilation equipment and the
fan when ventilation is needed.
Equipment Controls Fan: The thermostat
turns on the ventilation equipment when
ventilation is needed. The fan is controlled
by the equipment.
10090 Number of
Bedrooms
1 to 6 2 This ISU is only displayed when ISU10050
Ventilation Control Method is set to
ASHRAE.
10090 Size of house 1000 to 5000 sq. ft. (in
100 sq. ft. increments)
(90 to 460 sq. m.)
1000 sq. ft. This ISU is only displayed when ISU10050
Ventilation Control Method is set to
ASHRAE.
10100
Enter Equipment
Ventilation Rate
30 to 350 CFM (in 5
CFM increments)
(850 - 9900 LPM)
150 CFM This ISU is only displayed when ISU10050
Ventilation Control Method is set to ASHRAE
(Residential only). This is the CFM rating of
the ventilation equipment.
Table 5. Installer Setup (ISU)
ISU #
Installer Setup
Name Settings Default Notes