T10 PRO SMART THERMOSTAT WITH REDLINK
27 33-00462—01
10125 Ventilation
Priority
ASHRAE is Priority
Lockouts are
priority
ASHRAE is
Priority
Lockouts are Priority: The thermostat places
a priority on lockouts versus the ASHRAE
62.2 ventilation standard. The thermostat
will not run ventilation during the following
lockout conditions (if configured) unless you
manually call for ventilation:
Lockout Ventilation during Outdoor
Conditions (ISU 10130)
Lockout Ventilation during “Sleep”
program period. Note: This option is set
by the user on the Ventilation screen in
the Menu (under options).
ASHRAE is Priority: ASHRAE requires
additional ventilation following a long off
cycle.
The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor
lockouts and run ventilation. When using
this option, it is recommended to increase
the rate (CFM) of the ventilation equipment
to meet the ASHRAE 62.2 ventilation
standard in a shorter run time.
10130 Ventilation Low
Temperature
Lockout
Off, -20° F to 40° F in
5° F increments.
(Off, -29.0° to 4.5°C in
varying increments)
Off Requires either wired outdoor sensor or
Internet weather (thermostat connected to
Wi-Fi and registered to the app).
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 10130)” beginning on
page 36.
10130 Ventilation
High
Temperature
Lockout
Off 80° F to 110° F
(in 5° F increments)
Off
10130 Ventilation
High Dew Point
Lockout
Off
65° F to 85° F in 5°
F increments
(Off 26.5° C to 43.5° F
in varying increments)
Off Requires Internet weather (thermostat
connected to Wi-Fi and registered to the
app). Wired outdoor sensor doesn’t enable
this setting because wired sensors don’t
sense humidity.
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See “Ventilation — Outdoor Condition
Lockouts (ISU 10130)” page 36.
10170 Ventilator Core
Cleaning
Reminder
Off
3, 6, 9, 12 Calendar
Months
Off
10170 Ventilator Filter
Cleaning
Reminder
Off
3, 6, 9, 12 Calendar
Months
Off
11000
Number of UV
Devices
0, 1, 2 0 Some systems may have two UV devices,
one for the A-Coil and another for Air
Treatment. A replacement reminder can be
setup for each one. Select 0 if no UV devices
are installed.
11050 Replace UV
Bulb 1
Off, 6, 12, 24 Calendar
Months
Off
11050 Replace UV
Bulb 2
Off, 6, 12, 24 Calendar
Months
Off
Table 5. Installer Setup (ISU)
ISU #
Installer Setup
Name Settings Default Notes