Manual

T10 PRO SMART THERMOSTAT WITH REDLINK
33-00462—01 8
Setting Slider Tabs
Set R Slider Tab, see Fig. 10.
Use built-in jumper (R Slider Tab) to differentiate
between one or two transformer systems.
If there is only one R wire, and it is connected to the R,
Rc, or RH terminal on the old thermostat, set the slider
to the up position (1 wire).
If there is one wire connected to the R terminal and one
wire connected to the Rc terminal, set the slider to the
down position (2 wires).
Fig. 10.
Set U Slider Tab, see Fig. 11.
Use built-in jumper (U Slider Tab) for IAQ device.
•When the U Slider Tab is in the down position (2 wires)
the U contacts are a dry set of contacts.
If your IAQ device is powered by the cooling
transformer, move the U Slider Tab to the up position (1
wire). When this is done, the lower U terminal is
internally jumped to the Rc terminal. In this application,
you would hook up one wire from your IAQ device to the
upper U terminal and the other to the common side of
the cooling transformer. The 1 wire setting is most
commonly used when using a fresh air damper for
ventilation or using low speed fan for dehumidification.
See wiring examples on the next page.
Fig. 11.
WIRING
NOTES:
1. Use 18- to 22- gauge thermostat wire.
Shielded cable is not required.
2. Set the R Slider Tab on the UWP to the up posi-
tion (1 wire) for 1 transformer systems or the
down position (2 wires) for 2 transformer sys-
tems.
3. Set the U Slider Tab to the position shown for
IAQ wiring diagrams on pages 12-13.
Wiring Diagrams
Fig. 12. Heat only: gas or oil furnace.
9
M37789
M37790
W R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
M37813
1
COMMON REQUIRED.
G USED FOR INDEPENDENT FAN CONTROL ONLY. MOST HEAT
ONLY, GAS OR OIL FORCED AIR SYSTEMS DO NOT USE A FAN
(G) WIRE.
2
1
2
FURNACE
R/Rc
SWITCH UP
O/B
HEAT ONLY.
GAS OR OIL FURNACE.