Install Instructions

TP9600-TP9630 Pneumatic
Thermostats
INSTALLATION INSTRUCTIONS
GENERAL
The TP9600 Series pneumatic thermostat provides
proportional control for pneumatic actuators in heating,
ventilating, and air conditioning systems.
FEATURES
One, two, or three pipe
Direct Acting and Reverse Acting
One or two bimetal elements for Day-Night or
Heating-Cooling operation
High capacity or one pipe low capacity devices
Adjustable stops to limit setpoint adjustment
Replaceable Air Filter
Includes cover
SPECIFICATIONS
Air Pressure:
25 psi max
18 psi operating
Setpoint Pressure:
Factory set at 8 psi
Air Consumption:
0.011 scfm
Setpoint Range:
60 to 90 F typical
50 to 75 F setback
Throttling Range:
2 to 10 F, Factory set at 4 F
Air Connections:
5/32 barb fittings
Branch Line Port:
Self-Sealing tap accessible under cover
Maximum Ambient Temperature:
150 F
Mounting:
Vertical wall mount with plug in backplate
ACCESSORIES
14002430-001: Protective Guard, Standard
TG509F,G: Protective Versaguard, Key Lock
14004439-001: Setpoint Extension Lever
Common Repair Parts
14001865-001: Filter Cartridge Assembly
Kits
14004911-001: Adaptor Plate Assembly
This kit adapts the TP9600 to replace newer
Johnson, Powers, Robertshaw, and Kreuter
thermostats
14002573-001: Universal Modernization Kit
This kit adapts the TP9600 to replace older
Honeywell and other manufactures of larger
thermostats
Copyright © 1996 Honeywell Inc. All Rights Reserved