January 2009 UDA2182 Universal Dual Analyzer Product Manual 107
Sub-menu
selection
Parameter Selection or Range
of Setting
Parameter Definition
Address 0 to 999 (default = 0) Modbus RTU Slave ID – 0 is offline
Baud Rate 2400 (default)
4800
9600
19200
38400
57600
115200
Modbus RTU Baud Rate
Port Reset Off (default)
Enable
Enable selection resets the Communication card.
It should be enabled when configurations for
Ethernet are modified.
DHCP No (default)
Yes
When YES, D
ynamic Host Configuration Protocol
server automatically assigns a dynamic IP
address to UDA.
The set dynamic IP can be seen from “Comm
Status” display.
IpAddr Octet 1
IpAddr Octet 2
IpAddr Octet 3
IpAddr Octet 4
0 to 255 These parameters are visible only when DHCP
option is NO.
Allows you to assign Static IP address to the
UDA.
SbntMsk Octet 1
SbntMsk Octet 2
SbntMsk Octet 3
SbntMsk Octet 4
0 to 255 These parameters are visible only when DHCP
option is NO.
Allows you to assign Subnet Mask as per the
local network settings
Dflt Gtwy Octet 1
Dflt Gtwy Octet 2
Dflt Gtwy Octet 3
Dflt Gtwy Octet 4
0 to 255 These parameters are visible only when DHCP
option is NO.
Allows you to assign the Default Gateway as per
the local network settings
Ethernet
DNS Srvr Octet 1
DNS Srvr Octet 2
DNS Srvr Octet 3
DNS Srvr Octet 4
0 to 255 These parameters are visible only when DHCP
option is NO.
Allows you to assign the DNS server IP address
as per the local network settings