Input Calibration
144 UDA2182 Universal Dual Analyzer Product Manual January 2009
Step Action Screen
6
Press
Enter
IN 1 pH/ORP Cal
Sample Cal
Auto Buffer Cal
Buffer Group
pH Offset
pH Slope
Reset pH Offset
Reset pH Slope
Buffer Cal
IN 1 pH/ORP Cal
Sample Cal
Auto Buffer Cal
Buffer Group
pH Offset
pH Slope
Reset pH Offset
Reset pH Slope
Buffer Cal
Use
to select
”Auto Buffer Cal”
7
Put the unit in “Hold”
mode
Remove the electrode
from the process.
Rinse the electrode
thoroughly with distilled or
de-ionized water
8 Calibrating the pH Offset
Press
Enter
Follow the prompts at the top
and bottom of the screen.
“Place probe in Buffer 1”
The display will show the pH of
the buffer 1 solution as
measured by the electrode
system.
The reading will be automatically
adjusted to match the known pH
value stored in the UDA2182
memory.
“Press Enter when stable”
9
Once the reading is stable
Press
Enter
“Buffer 1 stability check”
Use
to change the value of
the Buffer.
“Up/Down changes Buffer”
10
Rinse the electrode thoroughly
with distilled or de-ionized
water
11 Calibrating the Slope
Press
Enter
Follow the prompts at the top
and bottom of the screen.
“Place probe in Buffer 2”
The display will show the pH of
the buffer 2 solution as
measured by the electrode
system.
The reading will be automatically
adjusted to match the known pH
value stored in the UDA2182
memory.
“Press Enter when stable”