Operating the Analyzer
January 2009 UDA2182 Universal Dual Analyzer Product Manual 27
Changing Parameters on the PID Display
When either PID Display is on the Display screen, you can edit the Setpoint value,
Setpoint Source, Control Mode, and the Output value. You can also enable or disable
Accutune and Tune Set.
Table 5-3 Changing PID Parameters on the Display
Press Action
Enter
to access the PID Parameters. You will see:
PID LOOP 1
LSP
Mode
Output
0.00
Manual
0.00
SP Source Local SP
Tune Set 2 Disable
PID LOOP 1
LSP
Mode
Output
0.00
Manual
0.00
SP Source Local SP
Tune Set 2 Disable
Example – PID Loop 1 Edit Display
to highlight the parameter you want to change.
Enter
to access the value or selection of each.
to change the value or selection.
Note: Output can only be changed in Manual mode.
Refer to “Section 6.4.1 – ”General Rules for Editing”.
Enter
to make the edit permanent.
Display
to return to the selected PID Display.